Daikin VRV III-S RXYMQ6PV4A Service Manual page 28

For high outdoor temperature use, r-410a
Table of Contents

Advertisement

SiME34-608
Slim Ceiling Mounted Duct Type (without Drain Pump)
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
3 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
6 Sound Level (H/L)
Safety Devices
Refrigerant Control
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable to set by the remote controller this pressure means "High static
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
Specifications
FXDQ20NVET
RT
0.7
kcal/h
2,000
Btu/h
7,800
kW
2.3
kW
2.2
RT
0.7
kcal/h
2,200
Btu/h
8,500
kW
2.5
Galvanized Steel Plate
mm
200×900×620
mm
2×12×1.5
0.176
Sirocco Fan
W
62×1
m³/min
9.5/7.5
Pa
44-15
5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
φ
mm
6.4 (Flare Connection)
φ
mm
12.7 (Flare Connection)
VP20
mm
(External Dia. 26 Internal Dia. 20)
kg
26
dBA
33/29
Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
difference: 0m.
difference: 0m.
0m. (Heat pump only)
pressure - Standard static pressure".
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
FXDQ25NVET
0.8
2,500
9,900
2.9
2.8
0.9
2,800
10,900
3.2
Galvanized Steel Plate
200×900×620
2×12×1.5
0.176
Sirocco Fan
62×1
9.5/7.5
44-15
5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
φ
6.4 (Flare Connection)
φ
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
C:3D049693
Specifications
FXDQ32NVET
1.1
3,200
12,600
3.7
3.6
1.1
3,400
13,600
4.0
Galvanized Steel Plate
200×900×620
2×12×1.5
0.176
Sirocco Fan
62×1
10.5/8.5
44-15
5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
φ
6.4 (Flare Connection)
φ
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Conversion Formulae
RT=kW×0.284
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
17