3.11 "C9 " Indoor Unit; C9" Indoor Unit: Malfunction Of Thermistor (R1T) For Suction Air - Daikin VRV III-S RXYMQ6PV4A Service Manual

For high outdoor temperature use, r-410a
Table of Contents

Advertisement

SiME34-608

3.11 "C9 " Indoor Unit:

Suction Air
C9
Remote
Controller
Display
Applicable
AII indoor unit models
Models
Method of
Malfunction detection is carried out by temperature detected by suction air temperature
thermistor.
Malfunction
Detection
Malfunction
When the suction air temperature thermistor becomes disconnected or shorted while the unit is
running.
Decision
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
Malfunction of Thermistor (R1T) for
Defect of indoor unit thermistor (R1T) for air inlet
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Connector
is connected to X13A
of the indoor unit
PC board.
YES
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the indoor
unit PC board.
(7.2kΩ~
112kΩ)
YES
Refer to thermistor resistance / temperature characteristics table on P229.
Troubleshooting by Indication on the Remote Controller
NO
NO
Connect the thermistor and turn
on again.
Replace the thermistor (R1T).
Replace the indoor unit PC board.
(V2786)
141