U3" Check Operation Not Executed - Daikin VRV III-S RXYMQ6PV4A Service Manual

For high outdoor temperature use, r-410a
Table of Contents

Advertisement

SiME34-608
"U3 "
3.40
Check Operation not Executed
U3
Remote
Controller
Display
Applicable
RXYMQ6P
Models
Method of
Check operation is executed or not
Malfunction
Detection
Malfunction
Malfunction is decided when the unit starts operation without check operation.
Decision
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
Check operation is not executed.
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Has the
check operation
performed on Outdoor
unit PC board?
YES
Troubleshooting by Indication on the Remote Controller
NO
Press the BS4 on PC board on the
master outdoor unit for 5 seconds
or more to execute check
operation.
Replace the main PC board on the
outdoor unit.
(V3052)
175