Daikin VRV III-S RXYMQ6PV4A Service Manual page 147

For high outdoor temperature use, r-410a
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
1: Coil check method for the moving part of the electronic expansion valve
Discount the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
×: No continuity
136
Pin No.
1. White
: Continuity
2. Yellow
3. Orange
×
Approx.
300Ω
×
4. Blue
5. Red
×
Approx.
150Ω
×
Approx.
300Ω
×
Approx.
150Ω
×
Troubleshooting
SiME34-608
6. Brown
×
Approx.
150Ω
×
Approx.
150Ω
×

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents