Battery Calculation; Device Current Consumption; Expro Panel In Various States; Expansion Boards - Zeta Premier EXPro Installation Manual

Hide thumbs Also See for Premier EXPro:
Table of Contents

Advertisement

EXPro Installation Manual

BATTERY CALCULATION

DEVICE CURRENT CONSUMPTION

EXPRO PANEL IN VARIOUS STATES

State
Mains fail, Buzzer silenced
Mains fail, Buzzer active
st
Mains failed, 1
Stage Alarm
nd
Mains failed, 2
Stage Alarm
Bottle released, Gas fired

EXPANSION BOARDS

Option
For each activated relay
3-relay expansion board (Standard)
8-relay expansion board (Optional)

EXTERNAL DEVICES

Item
Optical
Heat
Maxitone Sounder

DETERMINING BATTERY SIZE

To calculate the required battery backup capacity, we use the equation:-
Minimum battery Size = 1.25 x [(T
Where:
T
= Minimum time in hours required for the alarm [½ hour is most common time]
ALM
I
=
Total alarm current in amps for all devices connected to the alarm circuits
ALM
T
=
Standby time in hours for the system after mains failure [normally 24, 48 or 72 hr]
SBY
I
=
Quiescent current in amps of control panel in fault condition [because of mains
SBY
failure].
T
= Minimum time in hours required for the bottle output
BOT
I
=
Total current drawn by equipment connected to the bottle output
BOT
Approved Document No: GLT-212-7-1
Issue: 1.7 Author: MF/NRPJ Date: 05/07/2021
www.acornfiresecurity.com
Current Consumption
52mA
57mA
110mA
150mA
167mA
Quiescent
100uA
50uA
0mA
x I
) + (T
x I
ALM
ALM
SBY
www.acornfiresecurity.com
Current Consumption
12mA
40mA Max
100mA Max
Alarm
35mA
35mA
25mA
) + (T
x I
)]
SBY
BOT
BOT
Page 26

Advertisement

Table of Contents
loading

Table of Contents