Zeta Premier EXPro Installation Manual page 16

Hide thumbs Also See for Premier EXPro:
Table of Contents

Advertisement

EXPro Installation Manual
Use the NEXT and PREV button to cycle through items that can be disabled, pressing OK
toggles the item between the enabled/disabled states:
Zone 1
Zone 2
Gas Fired input
Manual release
Auto Manual
Abort Input
Low Pressure Input
Sounder 1A
Sounder 1B
Sounder 2
Bottle Output
External Fan
When an item is disabled the GENERAL DISABLEMENT LED will light, along with the
corresponding FLT/TEST/DISABLED LED.
Press CANCEL to exit out of the disablement menu, the item will remain disabled until it is
manually re-enabled.
Test: Allows the user/engineer to put an input or output into test mode.
Use the NEXT and PREV button to cycle through items that can be placed in test mode,
pressing OK puts the input into test mode.
When an input or output is in test mode the panel will indicate if it has been activated, but is
prevented from entering the normal sequence of events (such as activating sounders or
bottle output) associated with that input.
Note: Only one input/output can be programmed in test mode at any one time.
Approved Document No: GLT-212-7-1
Issue: 1.7 Author: MF/NRPJ Date: 05/07/2021
www.acornfiresecurity.com
Prevents the panel from responding to an alarm in zone 1
Prevents the panel from responding to an alarm in zone 2
Prevents the panel from responding to the gas fired signal
Prevents the panel from responding to a manual release
Prevents the external switching between auto and manual mode.
Switching between auto and manual mode can still be done from the
panel.
Disables the Abort input. The panel will not enter the alarm condition
if the abort input is disabled.
Prevents the panel from responding to a low pressure signal.
Disables sounder 1A
Disables sounder 1B
Disables the second stage sounder. The panel will not enter the
Activated condition if the second stage sounder is disabled.
Disables the bottle output. The panel will not enter the Activated
condition if the bottle output is disabled.
Disables the output to the external fan
*TEST MENU *
Low Pressure input
www.acornfiresecurity.com
Page 16