EXPro Installation Manual
option 5, Then as for the countdown timer select option 3 timers and press the next key until the
Release timer option is shown. Press enter to set the release time using the keypad and then press
enter to save the new time.
The release timer can be set such that it does not automatically timeout by changing the release
time to 99:99 (the display will change to 100:39). An unlimited release must be manually reset by
using the external abort input or by resetting the panel (Reset CIE) after the reset inhibit timeout.
The Reset Inhibit Timer prevents the panel being reset immediately after a release. This prevents a
panel from being reset, so that the system can be investigated by the responsible person to
determine the cause of the release. It can be set from 0 to 30 minutes. To set the reset inhibit timer
press enter option 5, Then as for the countdown timer select option 3 timers and press the next key
until the Reset inhibit timer option is shown. Press enter to set the Reset inhibit time using the
keypad and then press enter to save the new time.
Ext. Fan Delay Timer delays the start of the extract fan, so that it will not start the extraction while
the extinguishing sequence is active. To set the Ext Fan Delay Timer
Fan Time is the time the fan will run for once it has been started. The timer is set in the same way as
Approved Document No: GLT-212-7-1
Issue: 1.7 Author: MF/NRPJ Date: 05/07/2021
www.acornfiresecurity.com
*Change Timings*
Release Time
00:30
Press ENT. to Change
*Change Timings*
Reset Inhibit Time
01:00
Press ENT. to Change
*Change Timings*
EXT. Fan Delay Start
01:00
Press ENT. to Change
the other timers.
*Change Timings*
Fan Time
02:30
Press ENT. to Change