Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment
can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
Page 1
Symbio™ 500 Programmable Controller BMSY500AAA0100011 Symbio 500 Programmable Controller BMSY500UAA0100011 Symbio 500 Programmable Controller, made in the USA BMSY500ABA0100011 Symbio 500 Rooftop / Heat Pump Controller (RTU/HP) SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Page 2
Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Page 3
Non-Trane personnel should always follow local regulations. Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Revision History • Updates to the Trane Wi-Fi Module section. • In the Specifying an Equipment Configuration section, updated the number of software points available. • Updates to the General Data Specifications table.
Page 9
Revision History • Added part numbers to the Trane Wi-Fi Module. • Updated the number of software points available in the Task 5; Specifying an Equipment Configuration section. • Updated the General Information section.
The Symbio 500 is BTL certified as a B-BC profile device. A complete list of Trane certified devices is available at www.bacnetinternational.org. Note: The Symbio 500 programmable controller supports being a BBMB. This is a specific functionality and is different than the profile certification. The Symbio 500 cannot be a router.
(PI1 and PI2) pressure transducers). Point total Expansion Modules The Symbio 500 controller has 23 on-board points. The controller can be point-expanded by using expansion modules. The Symbio 500 can have an additional 110 points, for a total of 133 points BAS-SVX090B-EN...
• Digital multimeter Symbio User Interface (UI) The Symbio 500 controller offers a web-based user interface (UI) used for installation, integration, and service tasks. Connecting to Symbio UI 1. Connect a laptop to the USB service tool port using a USB 2.0 A to B cable. Symbio UI can only be accessed over USB connection.
X13651743002 Wi-Fi Field Installed Kit, 2.9 m cable, 70C Trane Connect The Symbio 500 module is Trane Connect enabled by either a Wi-Fi connection or via an Ethernet connection with the SC+ controller. The web UI is used to setup the module and connection.
Mounting the Symbio 500 Clearances Figure 2. Controller dimensions 2.17 in. 5.65 in. (143.5 mm) [8 units*] (55 mm) 1.73 in. (44 mm) 4.00 in. (101.6 mm) Note: DIN Standard 43 880, Built-in Equipment for Electrical Installations, Overall Dimensions and Related Mounting Dimensions.
Page 15
Mounting the Symbio 500 2. Gently push on lower half of device in the direction of the arrow until the release clip locks into place. To remove or reposition the controller: 1. Disconnect all connectors. 2. Insert a screwdriver blade into the slotted release clip (shown below) and gently pry upward to disengage the clip.
Wiring Overview General Instructions All wiring must comply with the National Electrical Code (NEC™) and local electrical codes. To connect wires to terminals when connecting wires to the Symbio 500 or XM30: BAS-SVX090B-EN...
BACnet/IP Over Wired Ethernet Communications Wired Ethernet is only an option on the Symbio 500 controller. Use daisy chain, star, or ring topologies. Air-Fi Wireless BACnet® Communications Symbio 500 can communicate wirelessly to the Trane Tracer SC+ and zone sensors through the Trane Air-Fi Wireless system (BACnet/Zigbee).
Three (3) BACnet links are available on the Tracer SC+. • Connect the BACnet link to the Symbio 500 controller terminals labeled Link as shown on the right. Incoming wires can be connected to the first two terminals, and the outgoing wires can be connected to the second set of terminals, so there is only one wire per termination.
Figure 5. Symbio 500 BACnet links Setting the Address The three (3) rotary address dials on the Symbio 500 serve one or two purposes depending upon the network: they are always used for the MAC Address, which is sometimes all or part of the BACnet Device ID.
It can be the same number as the MAC Address, determined by the rotary address dials on the Symbio 500 controller. For example, if the rotary address dials are set to 042, both the MAC Address and the BACnet Device ID are 042, OR •...
Sharing 24 Vac power between controllers could result in equipment damage. A separate transformer is recommended for each Symbio 500 controller. The line input to the transformer must be equipped with a circuit breaker sized to handle the maximum transformer line current.
Transformer Recommendations The Symbio 500 controller can be powered with 24 Vac or 24 Vdc. You must use a 24 Vac power supply for proper operation of the binary inputs, which require 24 Vac detection, and also to use the spare 24 Vac outputs to power relays and TRIACS.
If the sequence completes as described, the controller is properly booted and ready for the application code. d. If the power LED flashes red, a fault condition exists. Inputs/Outputs Pre-power Checks Before connecting any inputs/outputs to the Symbio 500 controller, perform the following pre-power checks. BAS-SVX090B-EN...
Page 24
• Binary inputs: check that they are opening and closing. Also check for 24 Vac if they provide their own power. With a Trane-provided 24 Vac, check to make sure it is dry contact and working. • Thermistors: check for 10K using a digital multimeter (DMM).
Page 25
Symbio 500 controller has been made and power has been applied. The step numbers in each illustration correspond to the information in each table. Note: The Symbio 500 controller should not be connected to the input and output devices during the pre-power checks, so the controller is not shown in the diagrams.
Page 26
Wiring Expected Value Checkout Procedure Measurement Vac ≈ 0.0 V Measure AC voltage across the current Step 1 AC voltage will affect further input. measurement. Measure DC voltage across the current Step 2 Vdc ≈ 0.0 V input. Compare the measured current with Measure the DC current across the the expected value based on the Step 3...
DO NOT run input/output wires or communication wires in the same wire bundle with AC power wires. Providing Low-voltage Power for I/Os The Symbio 500 controller can provide low-voltage power to the inputs/outputs. More than one input or output can receive power from a given screw terminal as long as the total amount of power consumed does not exceed the terminal’s limit.
Expansion Modules: If all analog outputs are configured for current and the devices are powered at the maximum current draw, then the XM30 maximum current draw is 115 mA. Do not exceed the Symbio 500 controller 200 mA output limit.
The pressure inputs P1 and P2 (shown in previous figure) are designed for 3-wire pressure sensor transducers, specifically Kavlico™ brand, which require 5 Vdc input. Important: If using a different brand of pressure sensor transducer, contact Trane for help ensuring proper operation.
Wiring Figure 10. Binary inputs Note: Polarity is normally open (NO) or ON. However, you can use the Polarity control (toggle) on the Binary Input Point Configuration dialog box to reverse polarity to normally closed (NC) or OFF. For example, you might reverse polarity when using a binary input with a freeze stat to open the contacts to shut off power when a temperature declines to a given setpoint.
Wiring Figure 11. 0–10 Vdc analog inputs To wire a 0–10 Vdc analog input: 1. Connect the shield wire (as common connection) to a common terminal. 2. Connect the signal wire to an available input terminal. 3. Connect the supply wire to a 24 Vdc or 24 Vac terminal as required. 4.
Wiring Figure 12. 0–20 mA analog inputs 24 Vdc 3-Wire 1000 ft 0-20 mA sensor (300 m) 0-20 mA Out (current source) max. Common Tape back shield wire, 2x 24 Vdc 2-Wire 0-20 mA sensor 0-20 mA Out (current controller) Shield Wire Shield Wire IM C...
3. .Use the Tracer TU service tool to configure the input for analog operation. Analog Outputs The Symbio 500 has two analog outputs. These outputs can be used for 0–10 Vdc outputs or 0–20 mA outputs, which can control actuators or secondary controllers. Output wiring specifications must comply with the receiving device wiring requirements.
4. Use the Tracer TU service tool to configure the input for analog operation. Relay (Dry Contact/Binary Outputs) The Symbio 500 has three relay binary outputs used as powered outputs. All outputs are isolated from one another and from the ground and power. The illustration below shows a typical wiring for relays, binary outputs.
Note: Polarity is normally open (NO) or ON. However, you can use the Polarity control (toggle) on the Binary Output Point Configuration dialog box to reverse polarity to normally closed (NC) or OFF. TRIAC Wiring The Symbio 500 has six (6) TRIAC binary outputs. The following illustrations show wiring to TRIAC binary outputs (low/high). BAS-SVX090B-EN...
Service Button LED • Binary Output Relay (3)/TRIAC (9) Status LEDs Figure 17. Symbio 500 LED locations LED Descriptions, Activities, and Troubleshooting The following table provides a description of LED activity, an indication or troubleshooting tip for each, and any relative notes.
Page 38
Operation Table 3. LED activities and troubleshooting tips Indication and Troubleshooting Tips LED Name Activities Notes Shows solid green when the unit is Indicates normal operation powered and no alarm exists. Shows blinking green during a device Indicates normal operation reset or firmware download.
Operation Table 3. LED activities and troubleshooting tips (continued) Indicates a corresponding binary If the user is currently powering the output has been commanded ON Symbio 400–B/500 from a USB port, the Led lights will turn ON. However, • Relay coil; indicates that a the binary outputs will not be command has been made to Shows solid yellow.
Page 40
Operation Table 4. Marquee LED status and error codes (continued) Message Description Action by User LED Blink Pattern Backup Retored Database backup has been restored. None- normal operation Updating Firmware Updating the firmware. None- normal operation Firmware Updated Firmware was updated. None- normal operation Updating Firmware Firmware is currently being updated.
Page 41
Operation Table 4. Marquee LED status and error codes (continued) Message Description Action by User LED Blink Pattern Try upgrading the controller firmware Kernel Update Failure Failed to update the kernel. again Replace controller. Device Tree Failure Failed to update the kernel device tree. Not applicable for 210, 400–B, or 600.
Configuration and Maintenance The Tracer TU service tool is used to configure and maintain a Symbio 500 (refer to the following Tasks 1 through 9). Because the Symbio 500 is a self-serviceable unit, this device is not intended to be disassembled by the user for maintenance.
Go to the information sources supporting one of the following options that was chosen: Option 1: Use the Tracer TU Configuration screen to create a factory configuration. Refer to the topics, VAV Boxes, Trane Factory Blower Coils, Fan Coils, and Unit Vents, or Variable Speed Water Source Heat Pumps in the Onlne Help.
Configuration and Maintenance Task 9; Backing Up/Restoring Files and Configurations Upload, back up, replace, or update configuration files, controller firmware, and TGP2 programs using the File Transfer Utility and the Backup Utility. Refer to the topics under Managing Configurations, Firmware, and Files in the Online Help. BAS-SVX090B-EN...
Maintenance Symbio controllers have no user-serviceable components. The controllers do not contain batteries or removable memory storage disks. No maintenance is required. If replacement is necessary, the best practice is to use Tracer TU to restore a user-created backup file. BAS-SVX090B-EN...
Commissioning and Troubleshooting in Powered State This section provides illustrations and methods about how to check the Symbio 500 points after making connection and applying power (indicated in each illustration by the terminal connector and Symbio 500 label). The step numbers or method numbers in each illustration correspond to the information in each table.
AC voltage will affect further measurement mode. measurement However, this method affects Measure DC voltage across the value of the Symbio 500 Step 2 Vdc ≈ 0.0 V the current input will use while controlling outputs. When the meter is...
Page 48
Commissioning and Troubleshooting in Powered State Expected Value General Information Checkout Procedure Measurement Method 2 interferes less in Vac ≈ 0.0 V Measure AC voltage across regards to the system. In Step 1 the voltage input voltage mode, the DMM AC voltage will affect further affects the circuit less.
General Information Checkout Procedure Measurement Checking the voltage that is Measure AC voltage with the powering the Symbio 500 is Symbio 500 connected. Step 1 20.0 Vac ≤ Vac ≤ 30.0 Vac often a necessary step when Perform this measurement commissioning or while the unit is under load.
The circuit within the pulse meter is completed when adding a pull-up resistance and reference voltage. On the Symbio 500, both universal input (UI) and analog output (AO) circuits add the necessary resistance and voltage without external parts.
Vref (reference voltage) provided by the UI or AO circuits of the Symbio 500. Most bipolar transistors have a Vsat of less than 0.2 Vdc. The DMM sampling rate may be too slow to measure pulse meter output transitions.
Commissioning and Troubleshooting in Powered State Binary Output, TRIAC High Side Switching, Methods 1 or 2 Expected Value Checkout Procedure Measurement Vac ≈ 0.0 V (TRIAC = OFF) Measure AC voltage across the binary Method 1 output Vac ≥ 24.0 V (TRIAC = ON) Vac ≈...
Commissioning and Troubleshooting in Powered State Binary Output, TRIAC Low Side Switching, Methods 1 or 2 Expected Value Checkout Procedure Measurement Vac ≈ 0.0 V (TRIAC = OFF) Measure AC voltage across the binary Method 1 output Vac ≥ 24.0 V (TRIAC = ON) Vac ≈...
Measure AC voltage across the voltage Vac ≤ 4.0 V chassis ground of the Symbio 500 needs termination and confirm that only one to be connected to earth ground by some end of the shield conductor is tied to the (Must comply with National Electrical route.
Resources • Air-Fi Wireless System IOM (BAS-SVX40*–EN) • Air-Fi Network Design (BAS-SVX55*–EN) • Air Systems for the Tracer SC+ Application Guide (BAS-APG036*–EN) • BACnet MS-TP Wiring and Link Performance Best Practices and Troubleshooting Guide (BAS- SVX51*–EN) • Tracer Graphical Programming 2 (TGP2) Editor Online Help •...
Page 56
For more information, please visit trane. com or tranetechnologies.com. Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.