Safety and Control Device Setting

• Compressor Protection
High Pressure Switch: This switch cuts out the
operation of the compressor when the
discharge pressure exceeds the setting.
Model
For Compressor
Pressure Switch
High
Cut-Out
Cut-In
Fuse
380-415V 3N~ 50Hz
380V 3N~ 60Hz
220V 3N~ 60Hz
CCP Timer
Setting Time
For Condenser Fan Motor
Internal Thermostat
DC
Cut-Out
AC
Cut-Out
Cut-In
For Control Circuit
Fuse Capacity on PCB1, 5
Fuse Capacity on PCB3
080
MPa
-0.05
4.15
-0.15
MPa
3.2+0.15
A
40
A
40
A
60
min.
3
o
120+5
C
o
135+5
C
o
110 60
~
C
A
5
A
10
28
• Fan Motor Protection
When the thermistor temperature is reached to
the setting, motor output is decreased.
The other way, when the temperature becomes
lower, limitation is cancelled.
100
Automatic Reset, Non-Adjustable
-0.05
4.15
-0.15
3.2+0.15
40
40
60
Non-Adjustable
3
Automatic Reset, Non-Adjustable
(each one for each motor)
120+5
135+5
~
110 60
5
10
120
-0.05
4.15
-0.15
3.2+0.15
40
40
60
3
120+5
135+5
~
110 60
5
10