Code
Category
01
Indoor Unit
Activation of Protection Device
02
Outdoor Unit
Activation of Protection Device
Abnormality between Indoor and
03
Transmission
Outdoor (or Outdoor and Outdoor)
Abnormality between Inverter PCB and Outdoor PCB
04
Transmission
Abnormality between Fan Controller and Outdoor PCB
05
Supply Phase Abnormality Power Source Phases
06
Voltage
Abnormal Inverter Voltage
07
Cycle
Decrease in Discharge Gas Superheat
08
Cycle
Increase in Discharge Gas Temperature
11
Inlet Air Thermistor
12
Outlet Air Thermistor
Sensor on
Indoor Unit
13
Freeze Protection Thermistor
14
Gas Piping Thermistor
19
Fan Motor
Activation of Protection Device for Indoor Fan
21
High Pressure Sensor
22
Outdoor Air Thermistor
Sensor on
23
Discharge Gas Thermistor
Outdoor Unit
24
Evaporating Piping Thermistor
29
Low Pressure Sensor
31
Incorrect Capacity of Outdoor Unit and Indoor Unit
35
Incorrect Setting of Indoor Unit No.
System
38
Abnormality of Protective Circuit in Outdoor Unit
Activation of Low Pressure Decrease Protection
43
Device
44
Activation of Low Pressure Increase Protection Device
Protection
45
Device
Activation of High Pressure Increase Protection Device
Activation of Low Pressure Decrease Protection
47
Device (Vacuum Operation)
48
Activation of Inverter Overcurrent Protection Device
51
Sensor
Abnormal Current Sensor
53
Inverter Error Signal Detection
Inverter
54
Increase of Inverter Fin Temperature
55
Inverter Failure
Outdoor Fan
57
Abnormality of Fan Motor
Motor
EE
Compressor
Compressor Protection Alarm
Outdoor Unit
b1
Incorrect Outdoor Unit No. Setting
No. Setting
Indoor Unit
b5
Incorrect Indoor Unit No. Setting
No. Setting
Table 7.3 Alarm Code
Content of Abnormality
27
Leading Cause
Activation of Float Switch, High Level in Drain Pan
Activation of PSH, Pipe Clogging, Excessive
Refrigerant, Inert Gas Mixing
Incorrect Wiring, Loose Terminals, Disconnect Wire,
Tripping of Fuse
Transmission Failure (Loose Connector)
Incorrect Power Source, Connection to Reversed-
Phase, Open Phase
Outdoor Voltage Drop, Insufficient Power Capacity
Excessive Refrigerant Charge,
Failure of Thermistor, Incorrect Wiring
Insufficient Refrigerant Charge, Pipe Clogging,
Failure of Thermistor, Incorrect Wiring
Incorrect Wiring, Disconnecting Wiring
Fan Motor Overheat, Locking
Incorrect Wiring, Disconnecting Wiring
Incorrect Setting of Capacity Combination
Duplication of Indoor Unit No.
Failure of Protection Detecting Circuit
(Failure of Protection Detecting Device, Abnormality
of Outdoor PCB, Incorrect Wiring of PCB)
Defective Compression (Failure of Compressor of
Inverter, Loose Power Supply Connection)
Overload at Cooling, High Temp. at Heating, Locking
(Loose Connector)
Overload Operation (Clogging, Short-Pass), Pipe
Clogging, Insufficient Refrigerant, Inert Gas Mixing
Insufficient Refrigerant, Refrigerant Piping Clogging,
Locking (Loose Connector)
Overload Operation, Compressor Failure
Current Sensor Failure
Driver IC Error Signal Detection (Protection for
Overcurrent, Low Voltage, Short-Circuit)
Abnormal Inverter Fin Thermistor, Heat Exchanger
Clogging, Abnormal Fan
Inverter PCB Failure
Disconnecting Wiring or Incorrect Wiring between
Control PCB (PCB1) and Fan Relay PCB (PCB3,
PCB5), Failure of Fan Motor
Failure of Compressor
Over 64 No. is Set for Address or Refrigerant Cycle.
More than 17 Non-Corresponding to H-LINKII Units
are Connected to One System.