York JDOH Series Original Instructions Manual page 16

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

(4) Fix the outdoor unit firmly so that declining,
making noise, and falling down by strong
wind or earthquake is avoided.
Fixing Plate
(Field-Supplied)
Both sides on the unit fixing
can be possible.
Fig. 4.9 Additional Fixing Arrangement
(5) When installing the unit on a roof or a
veranda, drain water sometimes turns to
ice in a cold morning. Therefore, avoid
draining in an area where people often use
because it is slippery.
(6) In case of the drain piping is necessary for
the outdoor unit, use the drain-kit
(DBS-26 or DBS-26L: Optional Parts).
Air Inlet
68
396
Drain Hole (2-φ26)
(Drain Boss Attaching Position)
(7) The whole of the base of the outdoor unit
should be installed on a foundation. When
using vibration-proof mat, it should also be
positioned the same way.
When installing the outdoor unit on a field-
supplied frame, use metal plates to adjust
the frame width for stable installation as
shown in Fig. 4.10.
When vibration measures
are necessary,
add vibration proof rubber.
(Field-Supplied)
Drain Hole
(3-φ24)
165
360
Incorrect
Outdoor Unit
is Unstable.
Frame
Correct
Outdoor Unit
is Stable.
Frame
Recommended Metal Plate Size (Field-Supplied)
Material: Hot-Rolled Mild Steel Plate (SPHC)
Plate Thickness: 4.5T
70
(560)
Fig. 4.10 Frame and Base Installation
9
Base Width of Outdoor Unit
100mm
Frame Width 60mm
(Field-Supplied)
Base Width of Outdoor Unit
100mm
Metal Plate
Metal Plate
100mm or more
4-C10
20
2-Long Hole
420
70