over and the UCB will de-energize the blower for 45 seconds.
However, the auxiliary limit is in series with the primary limit
and it takes first control. If the excessive heat has been high
enough to cause the auxiliary limit (AUX) to open, then the
ICB will flash the primary limit code but the furnace will not
retry ignition during the same call for heat. The auxiliary limit is
of the manual reset type and is mounted in the upper right
hand corner of the panel between the burner manifold and the
flue gas collector box just behind the draft motor. If the
auxiliary switch has opened, then special attention should be
paid to the primary limit as it may be faulty as well. However,
the auxiliary switch is sized such that multiple trips of the
primary limit due to complete blower failure will cause enough
heat to build up and trip the auxiliary.
If the primary limit opens three times within one hour, then the
UCB will lock on the indoor blower and flash a flash a code on
the Simplicity Lite Control (Table 31) or sends error message
to the LCD Smart Equipment™ Control.
Gas Valve
The UCB monitors the gas valve (GV). Any time the UCB senses
voltage at the GV without a call for heat for a continuous five-
minute period, the UCB will lock on the indoor blower and flash a
code on the Simplicity Lite Control (Table 31) or sends error
message to the LCD Smart Equipment™ Control. When the
UCB no longer senses voltage at the GV the UCB will de-
energize the indoor blower after the expiration of the indoor
blower heating off delay.
If the voltage has been sensed at the GV for at least 15
seconds during the fan on delay for heating and the UCB no
longer senses voltage at the GV (W1 call for heat removed or
an ICB fault exists), then the UCB forces the indoor blower on
for the indoor blower heating off delay.
The gas valve is of the redundant type. If for any reason the
main gas valve fails in the open position, then the redundant
valve ahead of the main gas valve will shut off the flow of gas to
both the pilot and main gas valves.
Centrifugal Switch
The centrifugal switch is mounted on the end of the draft motor
and it is an integral part of the motor assembly. On a call for
heat, the ICB checks the centrifugal switch (CS) for open state
before it energizes the draft motor. If it is closed, then the ICB
will lock out the furnace and flash a code (Table 32). If open,
then the ICB will energize the draft motor and verify that the
switch closes before initiating the purging and ignition
sequence. If at any time during furnace operation the
centrifugal switch opens, then the ICB will de-energize the pilot
and main gas valves and monitor the centrifugal switch. If the
centrifugal switch closes and the call for heat still exists, then
the ICB will retry the purging and ignition sequence.
Roll-out Switch
This temperature sensitive switch is located in the burner
vestibule just above the right hand side of the burner assembly.
In the event of the flame spilling out into the burner manifold
area the roll-out switch will open, the ICB will close both the
54
main and pilot gas valves and flash a code (Table 32). The ICB
will not retry the ignition sequence during the same call for heat.
Flame Sense Circuit
The flame sensor is mounted on the left hand side of the burner
assembly and is positioned such that the pilot flame surrounds
the tip of the sensor. On a call for heat the ICB checks for the
flame sense circuit to be open. If open, then the ICB initiates the
purging and ignition sequence. Once the pilot flame is present,
the ICB monitors the flame sense circuit for pilot flame stability.
If the pilot flame is unstable or lost completely, then the ICB will
immediately close both the pilot and main gas valves. The ICB
will retry the purging and ignition sequence. If the flame is
unstable or lost more than 16 times during the same call for
heat, then the ICB will lock out furnace operation for 5 minutes.
Table 23: Single Stage Gas Heat Limit Control Setting
Unit
Capacity, MBH
(Tons)
Input
Output
3
50
40
3
100
80
4
75
60
4
125
100
5
100
80
5
125
100
6
100
80
6
125
100

Flash Codes or Error Messages

The UCB will initiate a flash code associated with errors within
the system. Refer to flash a code on the Simplicity Lite Control
(See Table 32) or sent error message to the LCD Smart
Equipment™ Control.

Resets

Remove the call for heating by lowering the thermostat setting
lower than the conditioned space temperature. This resets any
lock outs.

Heat Anticipator Setpoints

It is important that the anticipator setpoint be correct. Too high
of a setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the
value below the correct setpoint will give shorter "ON" cycles
and may result in the lowering of the temperature within the
conditioned space.
Table 24: Gas Heat Anticipator Setpoints
Gas Valve
Honeywell VR8204M
White-Rogers 36E36

Start-up (Cooling)

Prestart Check List
After installation has been completed:
1.
Check the electrical supply voltage being supplied. Be sure
that it is the same as listed on the unit nameplate.
Limit Control Opens, °F
Direct Drive
Belt Drive
240
240
170
210
210
240
165
210
170
210
165
210
170
210
165
210
Anticipator Setpoints
0.60 amp
0.54 amp