Refrigerant Piping Work; Piping Materials - York JDOH Series Original Instructions Manual

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

5.

Refrigerant Piping Work

Use refrigerant R410A in the refrigerant cycle.
Do not charge oxygen, acetylene or other
flammable and poisonous gases into the
refrigerant cycle when performing a leakage
test or an air-tight test. These types of gases
are extremely dangerous and can cause an
explosion. It is recommended that
compressed air, nitrogen or refrigerant be
used for these types of tests.
5.1

Piping Materials

(1) Prepare locally-supplied copper pipes.
(2) Select the piping size from the Table 5.1.
(3) Select clean copper pipes. Make sure
there is no dust and moisture inside of the
pipes. Blow the inside of the pipes with
nitrogen or dry air, to remove any dust or
foreign materials before connecting pipes.
NOTE
G Cautions for Refrigerant Pipe Ends
When installing pipe through
the wall, secure a cap at the
end of the pipe.
Incorrect
Correct
Hole
Hole
Attach a cap
or vinyl tape.
Correct
Incorrect
Rain water can
enter.
Attach a cap
or vinyl bag with
rubber band.
Do not place the pipe
directly on the ground.
Correct
Incorrect
Attach a cap
or vinyl tape.
G Flaring Dimension
Perform the flaring work as shown below.
+ 2
90
o
o
qA
0.4 ~ 0.8R
qd
(/) It is impossible to perform the flaring
work with 1/2H material. In this case,
use an accessory pipe (with a flare).
G Piping Thickness and Material
Use the pipe as below.
Diameter
q6.35
q9.53
q12.7
q15.88
q19.05
q22.2
q25.4
q28.6
Material is based on a JIS standard (JIS B8607).
G Flare Nut Dimension
Use the flare nut as below.
<Flare Nut Dimension B (mm)
Diameter
q6.35
q9.53
q12.7
q15.88
q19.05
Dimension is based on a JIS standard
(JIS B8607).
G Cap the end of the pipe when the pipe is to
be inserted through a hole.
G Do not put pipes on the ground directly
without a cap or vinyl tape at the end of the
pipe.
10
Diameter
qd
6.35
9.53
12.7
15.88
19.05
R410A
Thickness
Material
0.8
O material
0.8
O material
0.8
O material
1.0
O material
1.0
1/2H material
1.0
1/2H material
1.0
1/2H material
1.0
1/2H material
R410A
17
22
26
29
Flare Nut
36
(mm)
+0
A
-0.4
R410A
9.1
13.2
16.6
19.7
(/)
(mm)
B