SIMPLEX 4120 NETWORK FIRE INDICATOR PANEL
OPERATOR MANUAL
2. Press the <ON> key. A typical display is shown below.
Press <ENTER> to force ON
SIGNAL CIRCUIT: 2:SIG3
3. Press the <ENTER> key. A typical display is shown below.
4TH FLOOR - EAST WING - STROBES
VISUAL
4. Press the <FLT ACK> key.
5. Press the <CLR> key. The display shows the following message.
** FAULT **
ALARMS=0
7.4

HOW TO RETURN A POINT TO AUTO

The <AUTO> key press leaves a point in its current state (ON or OFF), but lowers its priority
so that the system program can control it. AUTO is the normal state for all control points. A
fault exists if any control point is taken out of the AUTO state.
The point to be turned to AUTO must first be identified to the system. This is accomplished
by selecting/entering the required point on the alphanumeric display, and pressing the
<AUTO> key. If the <AUTO> key is passcode protected, perform the Log In Procedures.
To return a point to AUTO, perform the following procedure.
1. Ensure the point to be turned to AUTO is shown on the alphanumeric display. A
typical point (2:SIG3) is shown below.
4TH FLOOR - EAST WING - STROBES
VISUAL
2. Press the <AUTO> key. A typical display is shown below.
Press <ENTER> for AUTOmatic control
SIGNAL CIRCUIT: 2:SIG3
Document No: 4100-M004
Press <ACK> to review.
ISOLATES=0
June 1997
Page 51
ON
FAULTS=1
OFF
Issue 1.0