Page 48
SIMPLEX 4120 NETWORK FIRE INDICATOR PANEL
OPERATOR MANUAL
The Acknowledge Keys may also require passcodes to acknowledge abnormal conditions.
If you press an <ACK> key with insufficient access, an error message will be displayed. The
points will scroll with <ACK> key pressing to allow you to view the points on the list, but the
points will not be acknowledged. (See Log in Procedure for details.)

6.13 POWER UP SEQUENCE

Whenever power is applied to the 4120 FIP panel, or when the 4120 FIP Master Controller
microprocessor has been reset, the 4120 FIP self-tests its memory integrity and verifies
card configurations. Next, the 4120 FIP displays the system startup in progress messages,
followed by a fault condition. Battery fault conditions normally clear automatically.
The green POWER ON LED illuminates immediately after AC power is applied to the 4120
FIP. Make sure that the green LED is illuminated before connecting the battery power
harness.
IMPORTANT
To power up the 4120 FIP, apply 240 VAC to the unit. Wait until the GREEN POWER
ON LED has illuminate; then connect the battery power harness.
To power down the 4120 FIP, disconnect battery power harness; then, turn the 240 VAC
power OFF.
Document No.: 4100-M004
June 1997
Issue 1.0