Page 20
A GLOBAL ACKNOWLEDGE of a fault condition is accomplished in the following manner.
1.
Unlock and open the panel door.
condition.
** FAULT **
ALARMS = 0
2.
Press the <FAULT ACK> key under the flashing yellow LED. The alphanumeric display
will show area and type of fault. The tone alert will silence and the yellow LED will glow
steady.
FIRST FLOOR EAST WING
FIRE MONITOR ZONE
3.
Read the alphanumeric display, then investigate the problem to determine its cause.
• Restore or replace the defective device in accordance with device instructions.
• The fault will automatically clear when the problem has been corrected.
• After a delay, the alphanumeric display should show:
SIMPLEX AUSTRALIA
8:23:43
3.2

INDIVIDUAL ACKNOWLEDGE OPERATION DURING FAULT CONDITIONS

An INDIVIDUAL ACKNOWLEDGE of a fault condition is accomplished in the following
manner.
1.
Unlock and open the panel door.
condition.
** FAULT **
ALARMS = 0
2.
Press the <FAULT ACK> key under the flashing yellow LED. Repeat this step and read
the reports. The alphanumeric display will show area and type of fault. The tone alert
will silence and the yellow LED will glow steady.
FIRE MONITOR ZONE OPEN CIRCUIT FAULT
Document No.: 4100-M004
SIMPLEX 4120 NETWORK FIRE INDICATOR PANEL
The alphanumeric display will show the fault
Press <ACK> to review points
ISOLATED = 0
MON 25 JAN 95
The alphanumeric display will show the fault
Press <ACK> to review points
ISOLATED = 0
1ST FLOOR EAST WING
Press ACK key to acknowledge
June 1997
OPERATOR MANUAL
FAULT = 1
AZF1
OPEN CIRCUIT FAULT
SYSTEM IS NORMAL
FAULT = 1
ROOM 2
ALTERNATING
LINES
Issue 1.0