Page 2
Last Revision Date: March 15, 2016 For the most up-to-date information for this product and others, please contact Simplex, Inc. at (800) 637-8603 or visit us on the web at http://www.simplexdirect.com.
Table of Contents Warnings and Cautions ............1 Safety information symbols Cautions Description and Specification ..........4 Overview of Use Control System Cooling System Load System Safety Unpacking ................6 Included Components Primary Inspection Installation ................7 Load Bank Placement Installation Procedure Remote HMI installation Load Dump installation...
Page 4
Maintenance/Troubleshooting ..........21 General maintenance Each Operation Every 6 Months Troubleshooting Alarms and Warnings ............23 Alarms Warnings AppeNDIx A — pARTS LISTINGS ............25 AppeNDIx B — MODBUS CONTROLS ...........41 Modbus Control Directions AppeNDIx C — pRODUCT WARRANTY ..........45...
Page 5
Table of Figures Current draw at specific resolutions (in kilowatts) .......5 Air Flow ........................7 Ground Bus ......................8 Main Load Bus ....................8 Conduit Opening ....................8 HMI TBH........................9 Serial Adapter ....................9 TB-DC ........................9 Load Dump Jumper ..................10 Current Transformers ................... 11 CT Orientation ....................
Page 6
Option B - Communication (TCP/IP Data Logging) ......27 PLC Component list ..................28 Control Relays ....................30 Terminal Blocks ....................32 Option 010 - Space Heaters ............... 34 Center Subpanel .................... 36 Phase A Detail ....................37 Phase B Detail ....................38 Phase C Detail ....................
1 WARNINGS AND CAUTIONS The following images indicate important safety information: afety information This General warning symbol points out important SymbolS information that, if not followed, could endanger personal safety and/or property. This Explosion warning symbol points out potential explosion hazards. This Fire warning symbol points out potential fire hazards.
Page 8
to large cubic airflow requirements, exhaust temperature, and velocity. Do not point exhaust at any nearby surface or object that may be adversely affected by high temperature. This includes but is not limited to painted surfaces, tar paper and asphalt roofs, water sprinkler heads, fire alarms, and volatile material.
Page 9
equipment only while standing on such insulative mats. • The National Electrical Code (NEC), Article 250 requires the frame to be connected to an approved earth ground and/or grounding rods. This grounding will help prevent dangerous electrical shock that might be caused by a ground fault condition or by static electricity.
2 DeSCRIpTION AND SpeCIFICATION Simplex Saturn load banks are precision test instruments verview of designed to apply a selectable load to a power source and measure the source’s response. They are used for routine maintenance exercise to ensure the long-term reliability and readiness of the standby generator.
3 UNpACKING The following items are included with your load bank. If any nCluded of the following are not included, please contact Simplex Direct omponentS at 800-637-8603. 1. Load bank 2. Controller (remote or local) 3. Manual 4. Drawing package Optional equipment 1.
4 INSTALLATION Figure 1 Air Flow Normally equipped, Saturn load banks laCement intended outdoor installation. A forced air system, which discharges out of the top of the unit, cools the load elements Figure 1 Air Flow.) (See Load banks require large quantities of air circulation, Improperly so it is essential to install the...
Figure 2 Ground Bus 1. To bring in the source’s nStallation power cables, pull holes roCedure in the Conduit Opening, located in the bottom of the load bank’s control panel enclosure (see Saturn load Figure Conduit banks feature Opening). a power 2.
Figure 5 HMI TBH If your HMI is installed emote directly on the load bank, inStallation skip to the next section. 1. Mount the HMI where desired. 2. Connect the HMI to the Load Bank by swinging the HMI’s screen out to expose the TB-H terminal Figure 6 HMI block (see...
Load Dump Figure 8 feature is desired, remove Load Dump Jumper inStallation factory-installed jumper at TB-R 1–2 and connect customer-supplied Load Dump contacts to Figure 9 TB-R 1–2 (See Load Dump Jumper). To dump the load, open the customer-supplied contact. To enable load, close the customer-supplied contact.
Figure 9 If your load bank is urrent Current Transformers equipped with Metering, ranSformer Automatic Mode inStallation Regenerative Mode options, you will have to install current transformers your power cable. • For metering mode, install current transformers on the load bank leg of your power “Figure 13 system (see...
Figure 12 Current Transformer placement for Metering Figure 13 Current Transformer placement for Auto/Regen. Mode The first current transformer must be installed on Phase A, and the second must be installed on Phase C. 12 — Installation...
Figure 14 TB-COM modbuS The Saturn load bank supports Modbus inStallation protocol, implemented either as RS485 or TCP/ IP (which is an optional upgrade). To implement Modbus control monitoring, connect the load bank to your facility’s systems as follows: For RS485: Figure 15 Modbus Serial 1.
Figure 16 TB-SH Saturn load banks are eater equipped with space heaters inStallation for cold weather operation and to prevent condensation, which damage unit. The heaters require a dedicated power source independent control power at all times to prevent startup failure due to cold environments.
bmS/baS Figure 17 TBR The Polaris provides a set of Remote Signal Dry nStallation Contacts, which allow you to integrate the load bank into your Building Management System (BMS) or Building Automation System (BAS) The dry contacts provide an alarm message, letting you know if the load bank has failed.
1. General Settings 2. Automatic Mode Settings 3. Test Mode (Intended only for Simplex engineers) 4. Factory Setup (Intended only for Simplex engineers) You can access General Settings and Automatic Mode Settings by pressing their respective buttons.
6 OpeRATING INSTRUCTIONS Figure 20 Fan/Control 1. Start the generator or operation Power Disconnect Switch source being tested. CHeCkS 2. Ensure the load bank’s Fan/Control Power Saturn load Disconnect Switch, banks feature located on the unit’s door, a power is in the on position (see outlet in the Figure 21 Fan/Control control panel...
If any of three voltage or current values are significantly different from the other two, check the load bank for a blown fuse. If no blown fuse is found, contact Simplex service at 800-637-8603, ext. 4. Pressing “Alarm History” on this screen will bring up a list of Figure 27.)
7 AUTOMATIC MODe Figure 26 Setup Screen The Saturn load bank can be equipped with an optional automatic mode, which will extend your generator’s life by protecting it against wet- stacking and reverse current. Automatic Mode adds Figure 27 Automatic verview load when the load bank Mode Setup...
Figure 29 Automatic the preset maximum value, Mode Running it begins removing load until the draw is back within the designated range. Before activate etting Automatic Mode, you must utomatiC configure the load bank to interact with your generator. The values Enter the Automatic mode you will need setup screen by pressing the “F4 Setup”...
Page 27
8 MAINTeNANCe/TROUBLeSHOOTING The load bank has been designed to require minimum eneral maintenance. All components have been chosen for a long, maintenanCe reliable life. Two basic intervals of maintenance are required: each operation and every 6 months. • Check the air intake screens and louvers, fan and cooling chamber, and exhaust openings for any obstructions or peration foreign objects.
Page 28
Although Saturn load banks are designed with trouble-free rouble operation in mind, some problems can arise. Please consult the SHooting following table for solutions to the most common issues before contacting a Simplex service representative. Table 1 Troubleshooting Problem Solution Load bank...
Page 29
9 ALARMS AND WARNINGS Saturn load banks are protected by four types of sensors. 1. Intake temperature, which checks the incoming air to ensure the load elements can be adequately cooled. 2. Exhaust temperature, which checks the air temperature coming out the load bank. 3.
Table 2 Troubleshooting alarms Alarm Cause Solution Motor Fan blades blocked Clear obstruction Intake vents blocked Clear intake vents by debris, paper, etc Fan blades have come Tighten fan blade hub. loose from shaft Intake vents blocked Clear intake vents by debris, paper, etc Load bank pulling Ensure load bank was...
AppeNDIx A — pARTS LISTINGS Figure 30 Right Subpanel Layout Option D - Automation/ Metering page 26 Option E - Communication (TCP/IP Data Logging) page 27 page 28 Control Relays page 30 Terminal blocks/Service Outlet page 32 Option 010 - Space Heaters page 34 Parts listings - 25...
Page 32
Table 3 Option D - Automation/Metering Label Description Part Number Terminal Block, 4 TB-M 1 25678547 Connections, Black Terminal Block, 4 TB-M 2 25678546 Connections, Red Terminal Block, 4 TB-M 3 25678557 Connections, Blue Terminal Block, 4 TB-M 4, 6 25678536 Connections, Grey Terminal Block, 4...
Page 33
Table 4 Option B - Communication (TCP/IP Data Logging) Label Description Part Number Modular Controller and Protocol 24955043 Converter Ethernet Switch, 5 24955074 Port, Unmanaged Parts listings - 27...
Table 10 Phase A Detail Label Description Part Number Bus Bar, Single Pole, Bus Bar (vertical) 60044465G 750A, Phase A Fuse, 35A, Class T, 14074000 Fast Acting Fuse, 70A, Class T, RF7-34 14087000 Fast Acting Bus Bar, Nept/Mars, Bus Bar (horizontal) 60063693 0.250”...
Table 11 Phase B Detail Label Description Part Number Bus Bar, Single Pole, Bus Bar (vertical) 60044466E 750A, Phase B Fuse, 35A, Class T, 14074000 Fast Acting Fuse, 70A, Class T, RF8-35 14087000 Fast Acting Bus Bar, Nept/Mars, Bus Bar (horizontal) 60063693 0.250”...
Table 12 Phase C Detail Label Description Part Number Bus Bar, Single Pole, Bus Bar (vertical) 660044467G 750A, Phase C Fuse, 35A, Class T, 14074000 Fast Acting Fuse, 70A, Class T, RF9-36 14087000 Fast Acting Bus Bar, Nept/Mars, Bus Bar (horizontal) 60063693 0.250”...
Page 46
Table 13 Load Control Terminal Blocks Label Description Part Number Fuse, 1.5A, Time F1-2 14009500 Delay Fuse, 3.5A, Time 14019775 Delay Terminal Block, 4 TB-L 1 25678547 Connections, Black Terminal Block, 4 TB-L 2 25678546 Connections, Red Terminal Block, 4 TB-L 3 25678557 Connections, Blue...
Page 47
AppeNDIx B — MODBUS CONTROLS Table 14 Modbus Controls (Read/Write) Function Name Type Address Code Activate Coil 16586 Apply Load Coil 16704 Cancel Coil 16487 Cooldown KW To Floating Point 28911 Apply Modbus controls - 41...
Page 48
Table 15 Modbus Indications (Read only) Function Name Type Address Notes Code Exhaust Alarm Coil 16484 Fan Failure Coil 16485 Alarm Load Dump Coil 16486 Activated Coil 8193 Fan Running Floating Applied Load 29077 Point Regulate Mode Coil 16705 Active Regenerative Sensing Mode Coil...
Page 49
Table 15 Modbus Indications (Cont.) Function Name Type Address Notes Code Floating 28679 Point Floating Point 28681 Floating Point 28683 Floating Point 28685 (a) Load Banks with Automatic Load Regulation Only (b) Load Banks with Regenerative Power Sensing Only (c) Load Banks with Any Automation Option Only Modbus controls - 43...
Page 50
1. Ensure that “Regulate Mode Active” (16705) and odbuS “Regenerative Sensing Mode Active” (16706) are OFF, ontrol indicating that the load bank is ready for Modbus Control ireCtionS 2. Turn “Activate Fan” (16586) ON to energize the cooling fan 3. Verify fan is running by checking that “Fan Running” (8193 is ON 4.
Page 51
AppeNDIx C — pRODUCT WARRANTY SIMPLEX, Inc., warrants the industrial electrical control, test and accessory equipment and parts and accessories thereof to be the kind and quality described in SIMPLEX’s specifications and to be free from defects in material or workmanship under normal...
Page 52
At Simplex, we are experts at building products that meet our customers’ exact requirements. For a complete listing of Simplex products visit www.simplexdirect.com.
Page 53
LOAD BANK RENTAL AND SERVICE CENTERS Simplex Onsite can place Load Banks, Cables, Transformers, and Fuel Polish- ers rentals as well as service technicians at your fingertips anywhere in the United States quickly and cost effectively. For information call 855-767-5483 or visit www.simplexonsite.com.
Page 54
Simplex, Inc. 5300 Rising Moon Road Springfield, IL 62711-6228 (800) 637-8603 www.simplexdirect.com...
Need help?
Do you have a question about the Saturn Series and is the answer not in the manual?
Questions and answers