York YAFS018 Installation Manual page 37

Hide thumbs Also See for YAFS018:
Table of Contents

Advertisement

The Aurora 'Advanced' Control System cont.
Tool will allow configuration of this input for the action of:
• No Action
• Disable compressor operation until removed
• Go to On Peak thermostat settings until removed [Requires
Com T-Stat] (Future Release)
• Compressor limited to 50% or low cap until removed [dual
capacity or variable speed only] (Future Release)
• Disable compressor operation for 1/2 hr (can be removed
immediately) (Future Release)
Then Flash Code 7 on the Green LED for the 'On Peak' mode. And
On Peak will display on communicating thermostats.
Home Automation 1 and 2 Inputs
The Home automation inputs are simple closed contact inputs that
will trigger an AID Tool and thermostat alert for the homeowner.
These would require optional sensors and or equipment for
connection to the AXB board. With two inputs two different sensors
can be selected. The selected text will then be displayed on the
AID Tool and communicating thermostats. These events will NOT
alter functionality or operation of the heat pump/accessories and is
for homeowner/service notification only.
Home Automation 1 - E23 HA1
With a closed dry contact signal, this input will cause an alarm and
Alert Code 23 to indicate on the stat or flash on ABC. The AID Tool
will allow configuration of this input between the following selections:
• No Action
• Home Automation Fault [no lockout info only]
- Output from home automation system
• Security Alarm [no lockout info only]
- Output from home security
• Sump Alarm Fault [no lockout info only]
- Switch output from sump sensor
• Smoke/CO Alarm Fault [no lockout info only]
- Switch output from Smoke/CO sensor
• Dirty Filter Alarm [no lockout info only]
- Output from dirty filter sensor
Home Automation 2 – E24 HA2
With a closed dry contact signal, this input will cause an alarm and
Alert Code 24 to indicate on the stat or flash on ABC. The AID Tool
will allow configuration of this input between the following selections:
• No Action
• Home Automation Fault [no lockout info only]
- Output from home automation system
• Security Alarm [no lockout info only]
- Output from home security
• Sump Alarm Fault [no lockout info only]
- Switch output from sump sensor
• Smoke/CO Alarm Fault [no lockout info only]
- Switch output from Smoke/CO sensor
• Dirty Filter Alarm [no lockout info only]
- Output from dirty filter sensor
AFFINITY & AFFINITY ADVANCED SINGLE & DUAL CAPACITY SERIES INSTALLATION MANUAL
Monitoring Sensor Kits
Energy Monitoring
(Standard Sensor Kit on 'Advanced' models)
The Energy Monitoring Kit includes two current transducers (blower
and electric heat) added to the existing two compressor sensors so
that the complete power usage of the heat pump can be measured.
The AID Tool provides configuration detail for the type of blower
motor, power adjustment and a line voltage calibration procedure to
improve the accuracy, and a power adjustment setting that allows the
compressor power to be adjusted to match the unit's line voltage using
the provided tables. This information can be displayed on the AID
Tool or selected communicating thermostats. The TPCM32U04AYRK
will display instantaneous energy use while the color touchscreen
TPCC32U01YRK will in addition display a 13 month history in graph
form. Refer to Unit Start Up Energy Monitoring for configuration details.
Single Speed Power Adjustment
Model
208
012
0.99
018
0.99
022
0.99
030
0.99
036
0.99
042
0.99
048
0.99
060
0.98
070
0.96
Dual Capacity Power Adjustment
Unit
Model
Capacity
Full Load
026
Part Load
Full Load
038
Part Load
Full Load
049
Part Load
Full Load
064
Part Load
Full Load
072
Part Load
Refrigerant Monitoring (optional sensor kit)
The optional Refrigerant Monitoring Kit includes two pressure
transducers, and three temperature sensors, heating liquid
line, suction temperature and existing cooling liquid line (FP1).
These sensors allow the measurement of discharge and suction
pressures, suction and liquid line temperatures as well as
superheat and subcooling. This information will only be displayed
on the AID Tool.
Performance Monitoring (optional sensor kit)
The optional Performance Monitoring Kit includes three
temperature sensors, entering and leaving water, leaving air
temperature and a water flow rate sensor. With this kit heat
of extraction and rejection will be calculated. This requires
configuration using the AID Tool for selection of water or antifreeze.
37
Voltage
230
250
0.98
0.97
0.97
0.96
0.99
0.95
0.99
0.94
0.99
0.93
0.98
0.92
0.97
0.90
0.96
0.87
0.88
0.85
Voltage
208
230
250
0.99
0.99
0.96
0.99
0.99
0.93
0.99
0.97
0.91
0.99
0.94
0.83
0.94
0.91
0.85
0.91
0.84
0.75
0.95
0.9
0.79
0.92
0.83
0.71
0.94
0.86
0.73
0.92
0.81
0.65