(2 THRU 6 NOMINAL TONS) Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.york-geothermal.com Additional rating information can found at www.ahridirectory.org FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE...
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Table of Contents Model Nomenclature ............. . 4 General Installation Information .
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Model Nomenclature Model Vintage YAS – Affinity Outdoor Split * - Factory Use Only Stage Controls T – Dual Capacity A – Aurora Base Control Unit Capacity Future Options 026, 038, 049, 064, 072 0 –...
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL General Installation Information Safety Considerations Duct System All blower coil units/air coils must be installed as specified by the WARNING: Before performing service or manufacturer’s installation instructions; however, the following maintenance operations on a system, turn off main recommendations should considered to minimize noise and power switches to both units.
Page 6
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL General Installation Information cont. When utilizing the existing air coil or line set, only flushing direct contact with the tubing. Wide hanger strips which conform to compounds that vaporize should be used; which means they are the shape of the tubing are recommended.
Page 7
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL General Installation Information cont. Dual Fuel Systems In add-on Outdoor Split applications, the coil should be located in the supply side of the furnace to avoid condensation damage Outdoor split units can be connected to fossil fuel furnaces that to the furnace heat exchanger.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Water Quality In ground water situations where scaling could be heavy or where that the heat exchanger may require occasional flushing. Failure biological growth such as iron bacteria will be present, a closed to adhere to the guidelines in the water quality table could result in loop system is recommended.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Water Piping Residential split units are supplied standard with GeoLink swivel Flow Center Installation connections with P.T. ports. Flow centers FC1-GL or FC2-GL, as needed, may be internally mounted on the outdoor split, Two stub tubes with barbs are pre CAUTION: Water piping exposed to outside connected to the coax.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Electrical Connections General Accessory Relay Be sure the available power is the same voltage and phase as that A set of “dry” contacts has been provided to control accessory shown on the unit serial plate. Line and low voltage wiring must be devices, such as water solenoid valves on open loop installations, done in accordance with local codes or the National Electric Code, electronic air cleaners, humidifiers, etc.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Electrical Connections cont. Pump Power Wiring Figure 14: Pump Wiring 208-230/60/1 See Figure 14 for electrical connections from control box to pumps. FC1/FC2 style flow centers with fixed speed pumps connect to PB1 in the control box. Internal Loop Pump(s) 208-230/60/1...
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL The Aurora™ Control System Aurora ‘Base’ Control The Aurora ‘Base’ Control (ABC) System is a complete residential and commercial comfort system that brings all aspects of the HVAC system into one cohesive module network. The ABC features microprocessor control and HP, LP, condensate and freeze detection, over/...
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL The Aurora Control System cont. Aurora ‘Base’ Control Reset Configuration Mode The control is placed in reset configuration mode by holding the push button switch SW1 for 50 to 60 seconds. This will reset all configuration settings and the EEPROM back to the factory default settings.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL The Aurora ‘Base’ Control System cont. Safety Features Over/Under Voltage Shutdown - An over/under voltage condition exists when the control voltage is outside the range of 18 VAC to The following safety features are provided to protect the 30 VAC.
Page 20
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL The Aurora ‘Base’ Control System cont. Blower (G) - The blower will start immediately upon receiving a Aurora Interface and Diagnostics (AID) Tool thermostat G command. If there are no other commands from the The Aurora Interface and thermostat the ECM will run on “G”...
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Wiring Schematics Dual Capacity Split - 208-230/60/1 Flow Center Ext Pump 1/2 hp Total 208-230/60/1 Compressor Yellow(8) Pump Pump Gray(9) Blue Note 1 Violet(6) Ground Lug Black Tan(16) Green(17) Violet(7) Circuit Breaker Unit Power Supply Black(2) 208-230/60/1 Black...
Page 23
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Wiring Schematics cont. Dual Capacity Split - 208-230/60/1 cont. Aurora LED Flash Codes Legend Slow Flash 1 second on and 1 second off 100 milliseconds on and 100 milliseconds off Fast Flash Flash Code 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating Factory Low voltage wiring Thermistor...
Page 24
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Wiring Schematics cont. Dual Capacity Split with GeoStart - 208-230/60/1 Flow Center Ext Pump Blue 1/2 hp Total 208-230/60/1 Compressor Run Winding Yellow(8) Pump Pump GeoStart Blue Gray(9) Active Pink Black Start Note 1 Violet(6) Ground Lug Common...
Page 25
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Wiring Schematics cont. Dual Capacity Split with GeoStart - 208-230/60/1 cont. Aurora LED Flash Codes Legend Slow Flash 1 second on and 1 second off Fast Flash 100 milliseconds on and 100 milliseconds off Flash Code 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating Factory Low voltage wiring...
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Refrigeration Leak Testing If an air handler manufactured by others is used then refrigerant should be added to the Affinity Split factory pre-charge. Refrigerant The refrigeration line set must be pressurized and checked for should be added for liquid line length.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Refrigeration cont. Determining Subcooling Measure the temperature of the liquid line on the small refrigerant line (liquid line) just outside the split cabinet. This location will be adequate for measurement in both modes unless a significant temperature drop in the liquid line is anticipated.
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Unit Startup Before Powering Unit, Check the Following: 11. First stage heating will energize after a time delay. 12. Check the temperature of both the supply and discharge water NOTE: Remove and discard the compressor hold down shipping (see the Unit Operating Parameters tables).
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Refrigerant Circuit Guideline Head Suction Compressor Air Temp. Water Temp. Symptom Superheat Subcooling Pressure Pressure Amp Draw Differential Differential Under Charged System (Possible Leak) High Over Charged System High High High Normal High Normal/Low Normal Low Air Flow Heating...
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Troubleshooting Aurora Control System Refrigerant Systems NOTE: Refer to the Aurora Base Control Application and To maintain sealed circuit integrity, do not install service gauges Troubleshooting Guide and the Instruction Guide: Aurora Interface unless unit operation appears abnormal.
Page 34
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Startup and Troubleshooting Heating Cycle Analysis Measure suction temperature here at TXV bulb in heating modes. Measure suction temperature here Volts ____ Suct PSI____ at TXV bulb in cooling modes. Amps ____ Suct sat temp____ Suct temp____ Super heat____ Lineset...
Page 35
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Troubleshooting cont. Single Speed/Dual Capacity Startup/Troubleshooting Form 1. Job Information Model # Job Name: Loop: Open / Closed Serial # Install Date: Hot Water Generator: Y / N 2. Flow Rate in gpm SOURCE COAX LOAD COAX (Water-to-Water) HEATING...
AFFINITY DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL Preventive Maintenance Water Coil Maintenance Other Maintenance Filters Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to Filters must be clean to obtain maximum performance.