INSTALLATION MANUAL
AFFINITY
GEOTHERMAL HEAT PUMPS
SINGLE SPEED HYDRONIC
MODELS:
YAWS018 - 075
(1.5 THRU 6 NOMINAL TONS)
Due to continuous product improvement,
specifications are subject to change without notice.
Visit us on the web at www.york-geothermal.com
Additional rating information can found at
www.ahridirectory.org
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL

Advertisement

Table of Contents
loading

Summary of Contents for York YAWS018 - 075

  • Page 1 (1.5 THRU 6 NOMINAL TONS) Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.york-geothermal.com Additional rating information can found at www.ahridirectory.org FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL...
  • Page 3: Table Of Contents

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Table of Contents Model Nomenclature ............. . 4 General Installation Information .
  • Page 4: Model Nomenclature

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Model Nomenclature Model Vintage YAW – Affinity Water-to-Water * - Factory Use Only Stage Control Options S – Single Speed A – Aurora™ Base Controls (ABC) B – Aurora™ Advanced Controls (ABC AXB) Unit Capacity C –...
  • Page 5: General Installation Information

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL General Installation Information WARNING: To avoid equipment damage, do not Safety Considerations leave the system filled in a building without heat Installing and servicing air conditioning and heating during cold weather, unless adequate freeze equipment can be hazardous due to system pressure and protection levels of antifreeze are used.
  • Page 6: Water Quality

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Water Quality The heat exchangers and water lines in the units are copper General or cupronickel tube. There may be other materials in the Water-to-water heat pumps may be successfully applied building’s piping system that the designer may need to take in a wide range of residential and light commercial into consideration when deciding the parameters of the applications.
  • Page 7: Field Connected Water Piping

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Field Connected Water Piping General The proper water flow must be delivered to each unit Each unit is equipped with captive FPT water connections whenever the unit heats or cools. To assure proper flow, to eliminate ‘egg-shaping’...
  • Page 8: Open Loop Well Water Systems

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Field Connected Water Piping cont. Figure 9a: Open Loop Solenoid Valve Connection Option Open Loop Well Water Systems Typical quick operating external 24V water solenoid valve Always maintain water pressure in the heat exchanger by (type PPV100 or BPV100) wiring.
  • Page 9 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Field Connected Water Piping cont. Typical Closed Loop Earth Coupled Installation Earth Coupled Systems with Flow Center Once piping is completed between the unit, flow center and the earth loop, final purging and charging of the loop is needed.
  • Page 10: Potable Water Systems

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Potable Water Systems The 018 and 025 models can be equipped to provide domestic hot water generation. An optional factory- installed hot water generator coil may be provided with the 040, 050, 060, and 075 to assist with this process. Suggested Domestic Water Heater Hookup 30 psi Pressure...
  • Page 11: Potable Water Systems

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Potable Water Systems cont. Hot Water Generator Connections The heat reclaiming hot water generator coil is vented double- wall copper construction and is suitable for potable water. To maximize the benefits of the hot water generator a minimum 50-gallon water heater is recommended.
  • Page 12: Hydronic Section

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Hydronic Section General guidelines are shown below for component If there is a restriction in the screen, the system could go to selection and design/installation criteria for the piping 0 psi (0 kPa), potentially causing pumps(s) failure. A valve system.
  • Page 13: Hydronic Section

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Hydronic Section cont. If using a Geothermal Storage tank there will be two red Another option for connection is to connect the thermostat wires exiting out of the top of the tank. These red wries on the Geothermal Storage tank directly to “R”...
  • Page 14: Accessories And Options

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Accessories and Options Earth Loop Pump Kit (Field Installed) UPS15-42RU Three-Speed Pump Curve A specially designed one or two-pump module provides all UPS15-42RU 3-Speed Pump liquid fl ow, fi ll and connection requirements for independent UPS15-42RU (Low) single unit systems (230/60/1 only).
  • Page 15: Accessories And Options

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Accessories and Options cont. Geo Storage Tank Dimensions From Geo To Geo 59˝ Dip Tube 1˝ x 3˝ Nipple w/1˝ x 3˝ Nipple PRIMARY ANODE 39˝ - 80 Gallon 42˝ - 119 Gallon 8˝ HOT OUTLET 3/4˝...
  • Page 16: Electrical Data

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Electrical Data Compressor Unit Rated Voltage Load Source Total Unit Min Ckt Maximum Model Voltage Min/Max Pump Pump Fuse/HACR LRA* 208-230/60/1 187/253 48.0 16.2 18.5 208-230/60/1 187/253 14.1 73.0 25.5 21.3 24.8 208-230/60/1 187/253 20.0 115.0 40.3...
  • Page 17: Electrical Data

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Electrical Data cont. 208 Volt Operation Control Box Relocation All 208-230 volt units are factory wired for 230 volt The control box can be installed on the rear of the unit. To operation. To convert the unit from a 230V unit to a 208V relocate the control box, follow the procedures below.
  • Page 18: Wiring Schematics

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Wiring Schematics Aurora Control - 208-230/60/1 Violet/White (8) Black/White (1) Load Pump 5A Circuit Breaker Compressor 208-230/60/1 Pump Black/White (2) Violet/White (9) Blue 5A Circuit Breaker Black Black/White (3) Capacitor Source Pump Pump Pump 1/2 hp Total Tan(10) 208-230/60/1...
  • Page 19 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Wiring Schematics cont. Aurora Control - 208-230/60/1 Blue Notes Compressor 1 - Switch blue and red wires for 208V operation. Black 2 – HydroZone controller is an optional field installed accessory. Run Winding Blue IntelliStart 3 –...
  • Page 20 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Wiring Schematics cont. Aurora Advanced Control - 208-230/60/1 Violet/White (8) Black/White (1) Load Pump 5A Circuit Breaker Compressor 208-230/60/1 Pump Black/White (2) Violet/White (9) Blue 5A Circuit Breaker Black Black/White (3) Orange (12) Capacitor Ext Pump Pump Pump...
  • Page 21 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Wiring Schematics cont. Aurora Advanced Control - 208-230/60/1 Blue Aurora LED Flash Codes Slow Flash 1 second on and 1 second off Compressor Fast Flash 100 milliseconds on and 100 milliseconds off Flash Code 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating Black Random Start Delay (Alternating Colors)
  • Page 22: External Control

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL External Control An external controller is necessary for operation. For water storage tank set point control the HydroStat HZC, and HZ0 may be used. A field supplied aquastat may also be used as the external control to the heat pump. If zoning is required, the Hydrologic Zone Panels and Control system can provide up to eight zones of closed loop hydronic heating and cooling.
  • Page 23: Converting To A Dedicated Cooling Unit

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Converting to a Dedicated Cooling Unit Procedure to Convert a Heating Only Unit to a Cooling Only Unit All non-reversible units are built at the factory as dedicated heating units. Follow the procedures below to make the unit a dedicated cooling unit.
  • Page 24: Unit Startup

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Unit Startup Before Powering Unit, Check the Following: Configuring the Sensor Kits NOTE: Remove and discard the compressor hold down Configuring the Sensor kits shipping bolt located at the front of the compressor The Aurora Advanced Control allows Refrigeration, Energy, mounting bracket.
  • Page 25 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Unit Startup cont. f. Energy monitoring can be read on any of the following components: i. AID Tool – instantaneous information only ii. Symphony Web Portal via AWL device connected to Aurora Refrigerant Monitoring (optional sensor kit) The optional Refrigerant Monitoring Kit includes two pressure transducers, and three temperature sensors, heating liquid line(FP2), suction temperature and...
  • Page 26: The Aurora Base Control System

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL The Aurora Base Control System Aurora ‘Base’ Control Aurora ‘Advanced’ Control The Aurora ‘Advanced’ The Aurora ‘Base’ Control Control expands on the (ABC) System is a complete capability of the Aurora residential and commercial ‘Base’...
  • Page 27 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL The Aurora Base Control System cont. Service Device Description Aurora ‘Base’ Aurora 'Advanced' Allows setup, monitoring and troubleshooting of any Aurora Control. NOTE: Although the ABC has basic compatibility with all For Service For Service Aurora, new product features may not be available on older (Ver.
  • Page 28: Control Features

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL The Aurora Base Control System cont. Aurora ‘Base’ Control DIP Switch (SW2) SW2-1 (Source) FP1 Selection – Low water coil temperature limit setting for freeze detection. On = 30°F; Off = 15°F. SW2-2 (Load) FP2 Selection – On = 30°F; Off = 15°F SW2-3 RV –...
  • Page 29 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL The Aurora Base Control System cont. Fault Retry – in the fault condition, the control will stage off Over/Under Voltage Shutdown - An over/under voltage the outputs and then “try again” to satisfy the thermostat condition exists when the control voltage is outside the Y input call.
  • Page 30 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL The Aurora Base Control System cont. ABC Control Board Layout Aurora ‘Base’ Control LED Displays These three LEDs display the status, configuration, and fault codes for the control. These can also be read in plain LED1 LED2 FP1 –...
  • Page 31: The Aurora "Advanced" Control System

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL The Aurora ‘Advanced’ Control System cont. Advanced Hot Water Generator Control Aurora ‘Advanced’ Control Features (Domestic Hot Water Option) The Aurora ‘Advanced’ In lieu of the ‘Base Hot Water Generator Control’, the Control system expands on Advanced features an AID Tool selectable temperature limit the capability of the Aurora and microprocessor control of the process.
  • Page 32 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL The Aurora ‘Advanced’ Control System cont. Smart Grid-On Peak (SG) Input Home Automation 2 – E24 HA2 With a closed dry contact signal, this input will cause an The 'On Peak' input was designed to allow utilities to alarm and Alert Code 24 to indicate on the stat or flash utilize simple radio controlled switches to control the On on ABC.
  • Page 33: The Aurora "Advanced" Control System

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL The Aurora ‘Advanced’ Control System cont. Aurora ‘Advanced’ Control LED Displays These three LEDs display the status, configuration, and fault codes for the control. These can also be read in plain English via the Aurora AID Tool. Status LED (LED3, Green) Description of Operation Fault LED, Green...
  • Page 34: Reference Calculations

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Reference Calculations Heating Calculations: Cooling Calculations: LWT = EWT - LWT = EWT + GPM x C* GPM x C* HE = C* x GPM x (EWT - LWT) HR = C* x GPM x (LWT - EWT) NOTE: * C = 500 for pure water, 485 for brine.
  • Page 35: Pressure Drop

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Pressure Drop Vented Only Load Side Pressure Drop (psi) Model 30°F 60°F 80°F 100°F 120°F Pressure Drop (psi) Model 60°F 80°F 100°F 120°F 018R* 018H 025R* 025H 040H/R 7/13/09 NOTES: Temperatures are Entering Water Temperatures. 10.0 Double wall vented coax for heating potable water 12.5...
  • Page 36: Physical Data

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Physical Data Model Compressor (1 each) Scroll Factory Charge R410a, oz [kg] 44.0 [1.25] 58.0 [1.64] 70 [1.98] 68 [1.93] 104 [2.95] 110 [3.12] Coax & Piping Water Volume - gal [l]* .52 [1.97] .89 [3.38] 1.0 [3.94] 1.4 [5.25]...
  • Page 37: Operating Parameters

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Operating Parameters Heating Mode Entering Entering Suction Discharge Superheat Subcooling Load Temp (°F) Source Temp (°F) Pressure (psig) Pressure (psig) (°F) (°F) 52-67 195-227 8-16 5-15 67-82 208-235 7-14 6-14 95-113 216-245 7-14 6-12 124-144 225-255 8-19...
  • Page 38: Antifreeze Correction

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Antifreeze Correction Catalog performance can be corrected for antifreeze use. Please use the following table and note the example given. Heating Cooling Antifreeze % Pressure Antifreeze Type by wt Drop Load Source Load Source EWT - °F [°C] 80 [26.7] 30 [-1.1]...
  • Page 39: Troubleshooting Guideline For Refrigerant Circuit

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Troubleshooting Guideline for Refrigerant Circuit The chart below will assist in determining if measurements taken at the unit are within factory specifications and aid in accurate diagnosis (SYMPTOM) and repair. The chart is general in nature and represents whether a symptom would result in normal, high, or low readings from the typical operating range.
  • Page 40: Hr Data

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL HR Data Heat of Rejection (kBtuh) Table Load Flow-3 GPM Load Flow-4 GPM Load Flow-5 GPM Source Source EST °F 50°F 70°F 90°F 110°F 50°F 70°F 90°F 110°F 50°F 70°F 90°F 110°F 19.8 21.3 22.7 24.2 20.1...
  • Page 41 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL HR Data cont. Load Flow-8 GPM Load Flow-11.5 GPM Load Flow-15 GPM Source Source EST°F 50°F 70°F 90°F 110°F 50°F 70°F 90°F 110°F 50°F 70°F 90°F 110°F 61.9 66.6 71.3 75.9 63.8 67.8 71.9 75.9 65.7 69.1...
  • Page 42: He Data

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL HE Data Heat of Extraction (kBtuh) Table Load Flow-3 GPM Load Flow-4 GPM Load Flow-5 GPM Source Source EST °F 60°F 80°F 100°F 120°F 60°F 80°F 100°F 120°F 60°F 80°F 100°F 120°F 11.1 11.3 11.5 12.0 10.4...
  • Page 43 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL HE Data cont. Heat of Extraction (kBtuh) Table Load Flow-8 GPM Load Flow-11.5 GPM Load Flow-15 GPM Source Source EST °F 60°F 80°F 100°F 120°F 60°F 80°F 100°F 120°F 60°F 80°F 100°F 120°F 11.5 15.0 35.4 31.0...
  • Page 44: Heating And Cooling Cycle Analysis

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL DHW HE cont. 018 and 025 DHW Heat of Extraction (kBtuh) Table Load Flow-3 GPM Load Flow-4 GPM Load Flow-5 GPM Source Source EST °F 60°F 80°F 100°F 120°F 60°F 80°F 100°F 120°F 60°F 80°F 100°F 120°F...
  • Page 45: Troubleshooting Form

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Heating Cycle Analysis Cooling Cycle Analysis...
  • Page 46 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Startup and Troubleshooting Form Company Name: _________________________________ Company Phone No: ______________________________ Technician Name: ________________________________ Date: __________________________________________ Model No: ______________________________________ Serial No:_______________________________________ Owner’s Name: __________________________________ Open or Closed Loop: _____________________________ Installation Address: ______________________________ Installation Date: _________________________________ Check One Start up/Check-out for new installation Troubleshooting...
  • Page 47: Troubleshooting

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Troubleshooting Should a major problem develop, refer to the following 9. The internal winding of the compressor motor may be information for possible causes and corrective steps: grounded to the compressor shell. If so, replace the compressor.
  • Page 48: Preventive Maintenance

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Preventive Maintenance Keep all air out of the water lines. An open loop system 4. Connect a plastic hose from the circulating pump inlet should be checked to ensure that the well head is not to the bottom of a plastic five (5) gallon pail (refer to allowing air to infiltrate the water line.
  • Page 49: Service Parts

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Service Parts Aurora Controls Part Description 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 Compressor 34P657-01 34P583-01 34P621-01 34P580-01 34P616-01 34P614-01 Compressor Capacitor 16P002D18 16P002D20 16P002D36 16P002D25 16P002D41 16P002D41 Compressor Sound Jacket 92P504A05 92P504A05 92P519-01 92P519-02 92P519-02 92P519-02 Thermal Expansion Valve...
  • Page 50 AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Notes...
  • Page 51: Revision Guide

    AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL Revision Guide Pages: Description: Date: First Published 01 Jul 2013 Updated 018 Electrical Data 19 May 2014 Added Aurora Controls and “Advanced” Aurora Controls 14 June 2016...
  • Page 52 ©2016 The manufacturer has a policy of continual product research and development and reserves the right to change design and specifi cations without notice. York and Affi nity are registered trademarks of Johnson Controls, Inc., and are used with permission.