Affinity geothermal heat pumps dual capacity, 2 thru 6 nominal tons

Advertisement

Quick Links

Heating and Air Conditioning

INSTALLATION MANUAL

AFFINITY
GEOTHERMAL HEAT PUMPS
DUAL CAPACITY
MODELS:
MODELS:
YAP026 - 072
YAP026 - 072
(2 THRU 6 NOMINAL TONS)
(2 THRU 6 NOMINAL TONS)
Due to continuous product improvement, specifications are
Due to continuous product improvement, specifications are
subject to change without notice.
subject to change without notice.
Visit us on the web at www.york-geothermal.com
Visit us on the web at www.york-geothermal.com
Additional rating information can found at
www.ahridirectory.org
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the YAP026 and is the answer not in the manual?

Questions and answers

Summary of Contents for York YAP026

  • Page 1: Installation Manual

    Due to continuous product improvement, specifications are Due to continuous product improvement, specifications are subject to change without notice. subject to change without notice. Visit us on the web at www.york-geothermal.com Visit us on the web at www.york-geothermal.com Additional rating information can found at www.ahridirectory.org...
  • Page 3: Table Of Contents

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Table of Contents Model Nomenclature ............4 General Installation Information .
  • Page 4: Model Nomenclature

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Model Nomenclature 15-16 Model Type Vintage YAP – Affinity nity * – Internal Factory Use Only Compressor Type or Ty Packaging T – Dual Capacity Capa acity A – Standard Unit Capacity (MBTUH) city (M MBTUH) Insulation...
  • Page 5: General Installation Information

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL General Installation Information WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the unit. If applicable, turn off the accessory heater power switch. Electrical Before lifting, make sure the unit weight is shock could cause personal injury.
  • Page 6 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL General Installation Information cont. Slab Mounted Units Installing Roof (Curb) Mounted Roof curb not provided by unit manufacturer and must be The unit should be set on a solid, level foundation, outsourced. Check building codes for weight distribution preferably a concrete slab.
  • Page 7: Duct System

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL General Installation Information cont. Duct System Water Quality Duct flanges are provided on side air discharge units It is the responsibility of the system designer and installing to facilitate a duct connection. A flexible connector contractor to ensure that acceptable water quality is present and that all applicable codes have been met in is recommended for discharge and return air duct...
  • Page 8: Condensate Drain

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL General Installation Information cont. Contaminated Water Condensate Drain In applications where the water quality cannot be held to To facilitate complete condensate removal, the outdoor prescribed limits, the use of a secondary or intermediate package unit should be mounted level or slightly pitched heat exchanger is recommended to separate the unit from towards drain.
  • Page 9: Closed Loop Ground Source Systems

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Closed Loop Ground Source Systems IMPORTANT: A secondary freeze detection After pressurization, be sure to turn the venting (burping) thermostat is installed in the unit to automatically screw in the center of the pump two (2) turns open (water start loop circulator pump if the ambient will drip out), wait until all air is purged from the pump, then tighten the plug.
  • Page 10 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Closed Loop Ground Source Systems cont. Figure 5a: Primary/Secondary Wiring with Aurora Base Multiple Units on One Flow Center Control (no AXB Board) NOTE: This feature is only available in the Aurora Advanced Ext Pump Compressor Control package (AXB board), NOT the Aurora Base...
  • Page 11: Open Loop Ground Water Systems

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Open Loop Ground Water Systems Typical open loop piping is shown below. Always maintain NOTE: For open loop/groundwater systems or systems water pressure in the heat exchanger by placing water that do not contain an antifreeze solution, set SW2-Switch control valves at the outlet of the unit to prevent mineral #1 to the “WELL”...
  • Page 12: Electrical Connections

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Electrical Connections General Accessory Relay A set of “dry” contacts has been provided to control The heat pump, and if auxiliary heat is installed, must accessory devices, such as water solenoid valves on open have a separate electrical service with a field-supplied, loop installations, electronic air cleaners, humidifiers, etc.
  • Page 13: Electronic Thermostat Installation

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Electronic Thermostat Installation Position the thermostat subbase against the wall so that Figure 10: Thermostat Wiring (Y1 Style Signals) it is level and the thermostat wires protrude through the middle of the subbase. Mark the position of the 24VAC (Hot) subbase mounting holes and drill holes with a 3/16-inch 24VAC (Common)
  • Page 14: Auxiliary Heat Ratings

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Auxiliary Heat Ratings BTU/HR Model Size Compatibility Model Stages 208V 230V 208V 230V 036 - 042 049 - 072 EAM5* 12,300 16,300 EAM8* 19,400 25,900 EAM10* 24,600 32,700 EAL10* 24,600 32,700 1100 EAL15* 10.8 14.4...
  • Page 15: Electrical Data

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Electrical Data Dual Capacity Unit with Variable Speed ECM Motor Blower Total Compressor Rated Voltage Model Loop Motor Unit Circ Fuse/ Voltage Min/Max LRA** HACR 208-230/60/1 187/253 18.2 11.6 58.3 21.0 21.0 24.0 208-230/60/1 187/253...
  • Page 16: Blower Performance Data

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Blower Performance Data Dual Capacity ECM Blower Table without Zoning AIR FLOW SPEED SETTINGS MODEL 1175 0.50 1050 1075 1275 1500 0.50 1175 1375 1450 1025 1250 2075 038 W/1HP* 0.75 1425 1625 1750 1925...
  • Page 17 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Blower Performance Data cont. Setting Blower Speed - Variable Speed ECM Speed Setup - These screens allow the technician to select the “G”, low, high, and auxiliary heat blower speed for the ECM blower motor. Change the highlighted item using The ABC board’s Yellow Config LED will flash the current the ▲...
  • Page 18: Dimensional Data

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Dimensional Data FRONT SIDE LEFT SIDE RIGHT SIDE BACK SIDE 038 Overall Cabinet Front Electrical Knockouts Left Electrical Knockouts Side Discharge Configuraton Width Depth Height 7/8” 1-3/8” 1-1/8” 7/8” 7/8” 1-1/8” 7/8” 1-3/8” 1-1/8” N/A Pump N/A N/A Condensate 53.1...
  • Page 19 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Dimensional Data cont. BOTTOM FLOW 026 BOTTOM FLOW (BACK SIDE) BLOCK OFF PLATES Bottom Side Features Bottom Flow BBB CCC EEE FFF GGG HHH Configuraton Return Loop Discharge 21.3 29.5 15.4 14.5 18.7 10.9 21.3...
  • Page 20 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Dimensional Data cont. 2' MINIMUM CLEARANCE FOR SERVICE ACCESS 2' MINIMUM CLEARANCE FOR SERVICE ACCESS WATER IN WATER OUT Legend Return Air Return Air Access Supply Air Control Access Panel Compressor Access Panel Blower Access Panel Loop Connection Access...
  • Page 21: Physical Data

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Physical Data DUAL CAPACITY Model Compressor (1 each) Copeland UltraTech, Dual Capacity Scroll Factory Charge R410a, oz [kg] (Aluminum tube and fin air coil) 52 [1.47] 78 [2.21] 92 [2.61] 96 [2.72] 110 [3.12] ECM Blower Motor &...
  • Page 22: The Aurora™ Control System

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL The Aurora™ Control System Aurora ‘Advanced’ Control Aurora ‘Base’ Control The Aurora ‘Advanced’ The Aurora ‘Base’ Control Control expands on the (ABC) System is a complete capability of the Aurora residential and commercial ‘Base’...
  • Page 23 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL The Aurora Control System cont. Service Device Description Aurora ‘Base’ Aurora 'Advanced' Allows setup, monitoring and troubleshooting of any Aurora Control. NOTE: Although the ABC has basic compatibility with all For Service For Service Aurora, new product features may not be available on older (Ver.
  • Page 24: Control Features

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL The Aurora ‘Base’ Control System cont. Aurora ‘Base’ Control Field Selectable Options via Hardware DIP Switch (SW1) – Test/Configuration Button (See SW1 Operation Table) Test Mode The control is placed in the test mode by holding the push button switch SW1 for 2 - 5 seconds.
  • Page 25: Safety Features

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL The Aurora ‘Base’ Control System cont. Cycle with Blower - The accessory relay will cycle with Lockout – when locked out, the blower will operate the blower output. continuously in “G” speed. The Alarm output (ALM) and Lockout output (L) will be turned on.
  • Page 26 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL The Aurora ‘Base’ Control System cont. Secondary Freeze Detection - A freeze detection Cooling Operation thermostat is installed inside the cabinet to automatically In all cooling operations, the reversing valve directly tracks start the loop pump if temperature drops below 20˚F.
  • Page 27 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL The Aurora ‘Base’ Control System cont. Aurora ‘Base’ Control LED Displays Aurora Interface and Diagnostics (AID) Tool These three LEDs display the status, configuration, and The Aurora Interface and fault codes for the control. These can also be read in plain Diagnostics (AID) Tool is English via the Aurora AID Tool.
  • Page 28 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL The Aurora ‘Advanced’ Control System AWL – Aurora Weblink (if available) Aurora ‘Advanced’ Control Features (optional accessory) The Aurora ‘Advanced’ AWL is an add-on WiFi router that connects to the ABC Control system expands on and offers many features: the capability of the Aurora •...
  • Page 29 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL The Aurora ‘Advanced’ Control System cont. Home Automation 1 and 2 Inputs Monitoring Sensor Kits The Home automation inputs are simple closed contact Energy Monitoring inputs that will trigger an AID Tool and thermostat alert for (Standard Sensor Kit on ‘Advanced’...
  • Page 30 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL The Aurora ‘Advanced’ Control System cont. Special Modes and Applications Aurora ‘Advanced’ Control LED Displays Communicating Digital Thermostats These three LEDs display the status, configuration, and fault The Aurora controls system also features either mono- codes for the control.
  • Page 31: Reference Calculations And Legend

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Reference Calculations Heating Calculations: Cooling Calculations: LWT = EWT + LWT = EWT - gpm x 500 gpm x 500 LAT (DB) = EAT (DB) - LAT = EAT + cfm x 1.08 cfm x 1.08 LC = TC - SC TH = HC + HW...
  • Page 32: Wiring Schematics

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Wiring Schematics Aurora Base Controls with ECM and IntelliStart Green/Yellow For optional Flow Center and Water Valve For optional IntelliStart wiring schematics refer to Blue wiring schematics refer to appropriate schematic. appropriate schematic. Black Ru n Ca pac itor...
  • Page 33 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Wiring Schematics cont. Aurora Base Controls with ECM and IntelliStart cont. With optional EA Series 10kW Auxiliary Electric Heat Shown 1 - Use copper o r aluminum conductors. 208-230/60/1 2 – When Auxil iary Heat is installe d the BLK/WHT wire from CC-L1 to PB2-2 and the GRY/WHT wire from CC-L2 to PB2-1 must be removed (located in the heat pump control box).
  • Page 34 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Wiring Schematics cont. Aurora Base Controls with ECM and IntelliStart FP1 – 15 F/30 ECM PWM FP2 – 15 F/30 ABC SW2 Accessory Relay RV – B/O Fault DESCRIPTION SW2-4 SW2-5 Config ACC –...
  • Page 35 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Wiring Schematics cont. Aurora Base Controls with ECM and IntelliStart Wiring For Op onal IntelliStart Op on Internal Water Valve Blue Compresso r Or ange (29) Run Winding IntelliStart Blue Black/White (31) ACC COM Active Black...
  • Page 36 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Wiring Schematics cont. Aurora Advanced Controls with ECM and IntelliStart Green/Yellow For op onal Flow Center and Water For op onal IntelliStart wiring Blue Valve wiring schema cs refer to the schema c refer to the Black See Figure 1 for DHW wiring.
  • Page 37 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Wiring Schematics cont. Aurora Advanced Controls with ECM and IntelliStart cont. With optional EA Series 20kW Auxiliary Electric Heat Shown 60 AMP 60 AMP Legend BRK2 BRK1 Factory Low voltage wi ri ng Light emi tting diode - Green Factory Line vol tage wiring Fi eld l ow voltage wiring...
  • Page 38 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Wiring Schematics cont. Aurora Advanced with ECM and IntelliStart FP1 – 15 F/30 ECM PWM FP2 – 15 F/30 RV – B/O Fault Config ACC – Dip 4 ACC – Dip 5 CC –...
  • Page 39 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Wiring Schematics cont. Aurora Advanced with ECM and IntelliStart cont. IntelliStart Op on Blue Compresso r Run W inding IntelliStart Blue Active Black Pink Start Tan(6) Common Black Unit Power Supply 208-230/60/1 Wiring for Op onal Violet (8) Yellow (9)
  • Page 40: Unit Startup

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Unit Startup i. Brine Selection – for HE/HR Before Powering Unit, Check the Following: capacity calculation NOTE: Remove and discard the compressor hold down ii. Flow Meter – activates the flow meter shipping bolt located at the front of the compressor iii.
  • Page 41 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Unit Startup cont. iii. In the Sensor Kit Setup screen adjust the Performance Monitoring (optional sensor kit) ‘Base Voltage’ to the nearest value to that The optional Performance Monitoring Kit includes three is measured temperature sensors, entering and leaving water, leaving iv.
  • Page 42: Antifreeze Corrections

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Unit Startup cont. 14. If auxiliary electric heaters are installed, increase the heating setpoint until the electric heat banks are sequenced on. All stages of the auxiliary heater should be sequenced on when the thermostat is in the Emergency Heat mode.
  • Page 43: Correction Factor Tables

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Correction Factor Tables Air Flow Corrections (Dual Capacity Part Load) Airflow Cooling Heating cfm Per Ton % of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext of Clg 0.922 0.778...
  • Page 44: Operating Parameters

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Operating Parameters Dual Capacity Models First Stage Operation Cooling -- No Hot Water Generation Entering Water Water Flow Suction Pressure Discharge Pressure Water Temp Rise Air Temp Drop Temp °F gpm/ton Superheat Subcooling psig psig...
  • Page 45: Pressure Drop

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Pressure Drop Dual Capacity Pressure Drop (psi) Model 30°F 50°F 70°F 90°F 110°F full load part load full load part load full load part load full load part load full load part load 1/26/12...
  • Page 46: Compressor And Thermistor Resistance

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Compressor Resistance Thermistor Resistance Thermistor Microprocessor 208-230/60/1 Compressor Model Temperature (°F) Resistance (Ohms) Model No. Start 75757-70117 ZPS20K5E-PFV 1.21 - 1.39 1.52 - 1.75 57392-53234 ZPS30K5E-PFV 0.81 - 0.94 1.41 - 1.63 43865-40771 ZPS40K5E-PFV 0.48 - 0.55...
  • Page 47: Heat Of Extraction/Rejection

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Heat of Extraction/Rejection Dual Capacity Heat of Extraction (kBtuh) Heat of Rejection (kBtuh) Model 30°F 50°F 70°F 90°F 30°F 50°F 70°F 90°F 110°F 12.8 10.8 14.7 22.8 21.4 20.3 Part 13.3 11.3 15.4 20.9 22.9...
  • Page 48: Troubleshooting

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Troubleshooting Aurora Control System Refrigerant Systems NOTE: Refer to the Aurora Base Control Application and To maintain sealed circuit integrity, do not install service Troubleshooting Guide and the Instruction Guide: Aurora gauges unless unit operation appears abnormal. Compare Interface and Diagnostics (AID) Tool for additional information.
  • Page 49 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Troubleshooting cont. Water Leaving Water Blower Thermistor Coax Coil Flow Sensor Water Flow Meter Entering Water Thermistor Leaving Air Thermistor Wire Bundle In FP2 Sensor Blower Performance Option Only Compartment) Water Line View of Coax Performance Option Only Suction Suction...
  • Page 50 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Startup/ roubleshooting Form Controls Info: Dealer: ABC Version: AXB Version: Phone #: Date: IZ2 Version: Problem: T-Stat Version: Model #: Installed Sensors: Serial #: COOLING CYCLE ANALYSIS SAT °F °F Unit Amp Draw: Loop: Open Closed...
  • Page 51 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Troubleshooting cont. Single Speed/Dual Capacity Startup/Troubleshooting Form 1. Job Information Model # Job Name: Loop: Open / Closed Serial # Install Date: Hot Water Generator: Y / N 2. Flow Rate in gpm SOURCE COAX LOAD COAX (Water-to-Water) HEATING...
  • Page 52: Preventive Maintenance

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Preventive Maintenance Water Coil Maintenance Other Maintenance Filters Keep all air out of the water. An open loop system should be checked to ensure that the well head is not Filters must be clean to obtain maximum performance. allowing air to infiltrate the water line.
  • Page 53: Service Parts List

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Service Parts List Dual Capacity Units Parts List Compressor 208-230/60/1 34P640-01 34P641-01 34P642-01 34P643-01 34P644-01 Run Capacitor 208-230/60/1 16P002D19 16P002D20 16P002D18 16P002D31 16P002D31 Sound Jacket 92P504A16 92P504A16 92P504A16 92P504A16 92P504A16 Power Harness 11P781-01 11P781-01 11P781-01...
  • Page 54 AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Notes...
  • Page 55: Revision Guide

    AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL Revision Guide Pages: Description: Date: Document Created 23 Nov 2017 JM/MA...
  • Page 56 ©2017 The manufacturer has a policy of continual product research and development and reserves the right to change design and specifi cations without notice. York and Affi nity are registered trademarks of Johnson Controls, Inc., and are used with permission.