The Aurora Control System cont.
Service Device
Aurora Interface and Diagnostics
(AID) Tool
Add On Control Feature Kits
(field or factory Installed)
Geo Energy Monitoring Kit
Refrigeration Monitoring Kit
Performance Monitoring Kit
AXB Kit for advanced hot water
generator control, slaving, variable speed
pump, IntelliZone2
Add On Thermostats and Zoning
TP32U03YRK/04YRK- MonoChrome
Traditional Y1, Y2 Thermostat
TPCM32U04AYRK - MonoChrome
Communicating Thermostat
TPCC32U01YRK - Color Touchscreen
Communicating Thermostat
IntelliZone2 ● 24V
ZoningCompatibility
IntelliZone2
Zoning
®
AFFINITY & AFFINITY ADVANCED SINGLE & DUAL CAPACITY SERIES INSTALLATION MANUAL
Description
Allows setup, monitoring and troubleshooting of any
Aurora Control.
NOTE: Although the ABC has basic compatibility with all Aurora, new
product features may not be available on older AID Tools. To simplify
the basic compatibility ensure the version of AID is at least the same
or greater than the ABC software version.
Description
Monitors realtime power consumption of compressor, blower, aux heat
and pump. Requires thermostat TPCM32U04YRK, or TPCC32U01YRK.
AXB required.
Monitors realtime pressures, temperatures, superheat, and
subcooling. AXB required.
Monitors air and water temperatures, and water flow rate and
calculates heat of extraction/rejection. AXB required.
Added to Affinity Series for key features of advanced hot water
generator control, advanced loop control/slaving, IntelliZone2
communication, and variable speed pump control.
Description
Elite Stat with full English fault codes and alerts, traditional Y1, Y2
thermostat
Elite Stat with full English fault codes and alerts, communicating
thermostat. Monochrome thermostat allows instantaneous energy
measurement only.
4.3 in. color touchscreen communicating thermostat with full English
fault codes and alerts. Color thermostat allows instantaneous and 13
month history.
IntelliZone2 ● 24V is a non-communicating zoning system requiring
Y1, Y2 signals that controls up to 4 zones (dual capacity) and 2
zones (single speed). For heat pumps without the optional AXB
board.
Includes color main thermostat and up to 6 zones (with variable
speed), 4 zones (with dual capacity), and 2 zones (with single
speed). There are 3 thermostat options (MasterStat, SensorStat,
ZoneStat). Requires AXB.
31
Aurora 'Base'
Aurora 'Advanced'
For Service
For Service
(Ver. 1.xx or greater)
(Ver. 2.xx or greater)
Aurora 'Base'
Aurora 'Advanced'
-
Standard
-
Optional Sensor Kit
-
Optional Sensor Kit
Optional
Standard
(field Kit)
Aurora 'Base'
Aurora 'Advanced'
Optional
Optional
Optional
Optional
Optional
Optional
Optional
(5 Speed ECM or
Optional
Variable Speed ECM
(IntelliZone2 Preferred)
Preferred)
Optional
-
(IntelliZone2 Preferred)