Contec Conprosys CPS-MC341-ADSC1-111 Reference Manual page 29

Multi-function modules
Hide thumbs Also See for Conprosys CPS-MC341-ADSC1-111:
Table of Contents

Advertisement

CPS-MC341-ADSC1-111, CPS-MC341-ADSC2-111, CPS-MG341-ADSC1-111 Reference Manual (Hardware)
SW3, SW4 (CPS-MC341-ADSC2-111)
CPS-MC341-ADSC2-111 has the RS-422A/485 setting up DIP switch and LED indicator. DIP switch
and LED Indicator are placed on the top of the product.
The factory default of all switches are set to "OFF".
SW4
1 2 3 4
DIP Switch
SW
Bit No.
ON/OFF
SW4
1
2
3
4
SW3
1
2
LED Indicator (Top)
LED
Color
TX
Yellow
RX
Yellow
Product Nomenclature and Function
SW3
RX
TX
1 2
ON
Enable the TX Terminator
OFF
Disabled the TX Terminator
ON
Enable the RX Terminator
OFF
Disable the RX Terminator
ON
Internal connection state of TX+ and RX+: Short(Half Duplex)
OFF
Internal connection state of TX+ and RX+: Open(Full Duplex)
ON
Internal connection state of TX- and RX-: Short(Half Duplex)
OFF
Internal connection state of TX- and RX-: Open(Full Duplex)
ON
RTS Communication Mode: Half Duplex
OFF
RTS Communication Mode: Full Duplex
-
System Reservation: Always OFF
Display
Flashing
It flashes upon transmitting data by the RS-422A / 485.
Flashing
It flashes upon receiving data by the RS-422A/485.
— 29 —