Pulse meter value:
This parameter corresponds to the nominal value of the pulse meter. For
example, the UValve incorporate a pulse generator of 328 Pulses per litre. The
allowed range is 10 to 1000 pulses per litre.
SV aperture delay
Regulates the time the solenoid valve takes to open after the transaction
confirmation. The allowed range is 0 to 600 seconds.
Suspension time
It regulates the pause time without receiving pulses from the pulse generator.
If the transaction is interrupted for a time longer than this value, the
transaction is counted as finished and the solenoid valve closes automatically.
The allowed range is 0 to 900 seconds.
Top Up time
It regulates the waiting time after the initial transaction is completed, making it
possible to do an additional topping in the same transaction although the preset
quantity is achieved. After this stated time it is not possible to dispense an
additional quantity to the transaction and it is considered as completed. For
example, we have ordered 4 litres and after that these 4 litres have been
dispensed, this is the time available for making an additional topping to the
original transaction (for example another 0.2 litres, because even if we initially
thought that the crank case had 4 litres, when the 4 litres are dispensed and
the dip stick is checked we see that we need to fill in a little more). During this
NexU INSTALLATION MANUAL
Rev 3 (XXXX 2019)
82