1MRK 511 209-UEN -
5.7.2.1
REC650
Commissioning Manual
•
Protection or control unit, Intelligent electronic device (IED), configured and
with settings entered.
•
Configuration diagram for the IED
•
Terminal diagram for the IED, or plant circuit diagram including the IED
•
Technical reference manual for the IED
•
IED test set for secondary injection
•
Means to indicate, measure and record operation and times, e.g. an event
recording facility
•
A bi-stable relay (BR) or two auxiliary relays to simulate a CB
•
Two push-buttons (SC, ST) to operate the BR and a change-over switch (SRY)
to simulate CBREADY
•
Possibly a switch simulation the Synchrocheck (SYNC) condition
IED
SMBRREC - CLOSECB
Trip
SMBRREC - CBPOS
SMBRREC - CBREADY
EN09000206 V1 EN
Figure 14:
Simulating the CB operation by a bi-stable relay/breaker simulator
and manual switches
Preparation of the verification
Procedure:
1.
Check the function settings.
In the HMI tree they are found under:
Main menu/Settings/IED Settings/Control/SMBRREC(79,0->1)/
1:SMBRREC
If any timer settings are reduced to speed-up or facilitate the testing, they
shall be set to normal after testing. A temporary label on the unit can be a
reminder to restore normal settings after which a verification test should be
performed.
2.
Decide if a synchronization check (SYNC) shall be included in the test.
Testing functionality
BR
SC
ST
SRY
To test
set
+
-
IEC09000206_1_en.vsd
Section 5