1MRK 511 209-UEN -
REC650
Commissioning Manual
5.
Measure the operate time of the timer by injecting a current two times the set
INcosPhi> value and the polarizing voltage 1.2 · UNRel>.
Tinv = kSN · Sref / 3I
0test
EQUATION2228 V1 EN
6.
Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7.
Set the polarizing voltage to zero and increase until the boolean output signal
UNREL is activated, which is visible in the Application configuration tool in
PCM600 when the IED is in online mode. Compare the voltage with the set
value UNRel>.
8.
Continue to test another function or complete the test by setting the test mode
to off.
IEC06000650 V2 EN
Figure 9:
Characteristic with ROADir restriction
· cos (φ)
3I
0
j
3 ×
j
I
cos
0
ROADir
Section 5
Testing functionality
o
=
RCADir
0
Operate area
-
=
3
U
U
0
ref
IEC06000650_2_en.vsd
(Equation 1)
43