ABB Relion 650 Series Commissioning Manual page 52

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 5
Testing functionality
44
Instrument
transformer
angle error
IEC06000651 V2 EN
Figure 10:
Explanation of RCAcomp.
Operation mode 3I
0
Procedure:
1.
Set the polarizing voltage to 1.2 · UNRel> and the phase angle between
voltage and current to the set characteristic angle (RCADir), the current
lagging the voltage.
2.
Measure that the operate power is equal to the SN> setting for the set
directional element.
Note that for operation, both the injected current and voltage must be greater
than the set values INRel> and UNRel> respectively.
The function activates the START and STDIRIN outputs.
Measure with angles j = RCADir +/- 45° that the measuring element operates
3.
· cos (RCADir - j) = 3I0 · 3U0 · cos(+/-45) =SN>.
when 3I
· 3U
0
0
4.
Compare the result with the set value. Take the set characteristic into
consideration, see figure
5.
Measure the operate time of the timer by injecting 1.2 · UNRel> and a current
to get two times the set SN> operate value.
a
RCAcomp
3I
(to prot)
3I
(prim)
0
0
· 3U
· cosφ
0
9
and figure 10.
1MRK 511 209-UEN -
RCADir = 0º
Operate area
-3U
=U
0
ref
Characteristic after
angle compensation
en06000651.vsd
Commissioning Manual
REC650