Technical Data / Operating Times - Siemens NXAIR Operating Instructions Manual

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Panels with motor operating mechanism control

27.19 Technical data / operating times

Item
Functional unit
number
Voltage supply for
1.
control circuit and motor circuit
2.
Power consumption of control circuit
3.
Energizing when the command is given
Power consumption of geared motor for
4.
racking function
5.
Motor running time for racking function
Feedback monitoring time for racking
6.
valid switching functions:
Racking to service or test position
412
Technical data
Wide-voltage range 24 V DC / 48 V DC / 60 V DC /
110 V DC / 220 V DC / 110 V AC / 230 V AC
Control and motor circuit are executed separately
Voltage fluctuations in the range from 0.85 × U
1.1 × U
are permissible
n
< 100 mA in operating mode
Until the motor starts up > 180 ms
110 V DC:
Motor starting current, approx. 6.5 A
Continuous motor current while racking, approx. 1 A
Motor power, approx. 1.2 W
Further values on request.
< 65 s
After giving the command and when a motor has
started, a fault signal is issued if the feedback
contacts detect no end position within 65 s.
Fault indication and fault evaluation according to
chapter 26.20.
NXAIR / ≤ 40 kA
to
n
110-0134.9 / 14