Siemens NXAIR Operating Instructions Manual page 192

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Operating the contactor panel with panel width 600 mm
When inserting a new HV HRC fuse-link, the striker pin must always point to the lower clamp. The position of
the striker pin is marked on the HV HRC fuse-link by a triangle representing an arrow (8).
Fig. 345: Seen from right side of truck: Striker pin pointing to lower clamp
Permissible HV HRC fuse-links
The specified SIBA HV HRC fuse-links are motor protection back-up fuse-links according to IEC 60282-1.
The dimensions of the HV HRC fuse-links correspond to DIN 43625.
192
NOTICE
Maloperation
Contactor
trucks
are
HV HRC fuse-links. Using the different type of fuse-links may cause damages on
the panel.
Use only the fuse-link types listed in the following table.
Do not mount bridging links instead of HV HRC fuse-links.
NXAIR / ≤ 40 kA
exclusively
designed
8
for
operation
with
specific
110-0134.9 / 14