Siemens NXAIR Operating Instructions Manual page 238

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Operating the switch-disconnector panel
Fig. 423: The position of the striker
Proceed in the same way with the other HV HRC fuse-links.
The HV HRC fuse-links have been replaced.
238
INFORMATION
Final procedure steps
Now the panel can be integrated into the course of operation again, for example:
Close the high-voltage door.
Switch the feeder earthing switch to OPEN position.
Insert the operating lever in the actuating opening of the switch-fuse
combination.
Turn the operating lever completely to the end position and switch strongly
towards the OPEN position again. This makes the toggle fastener latch
tight again and the switch-fuse combination can now be closed.
Close the switch-fuse combination.
NXAIR / ≤ 40 kA
110-0134.9 / 14