Advertisement

Remove both HV HRC fuse-links from the second outer phase in the same way.
Fig. 349: Rear side of truck: All HV HRC fuse-links
After removing the HV HRC fuse-links from the outer phase L3, the fuse-links in the middle
phase are accessible from the right side of the contactor truck.
Remove both HV HRC fuse-links from the middle phase.
Fig. 350: Removing HV HRC fuse-links
110-0134.9 / 14
Operating the contactor panel with panel width 600 mm
removed from outer phases
from the middle phase
NXAIR / ≤ 40 kA
195