1.4 K3000 Setup Mode
Setup mode allows the Controller to be set for language displays, vat sizes, and temperature range displays. Follow the
steps below to enter and navigate Vat Setup.
Vat Set Up
Left Display
Right Display
OFF
OFF
Product Setup
Blank
Vat setup
Enter code
System
Blank
Language
English
2nd language
English
Locale
Non-ce
ENERGY
Gas
type
KJ3 Full
System volume
9
Tempr format
F
Exit Melt Tempr
100F
Setback tempr
250F
Fresh oil
None
waste
NONE
DRAIN SWITCH
NO
RECOVERY
DISABLED
ALARM
Exit
Exit
OFF
OFF
Time/date
Blank
Time entry
time
Date format
Mm/dd/yy
Enter date
date
Exit
Exit
Continued on the following page
Press and hold until Product Setup is displayed.
Press to scroll to Vat setup and press . Product setup is described on pages 1-10
through 1-13.
Enter 3228.
Press button or press to scroll to Time/Date, Filter, E-Log, Change Password or Edit
Alarm Names. With desired choice displayed, press . If SYSTEM is not chosen skip to
the relevant selection.
Press to scroll to choice and press .
Press to scroll to choice and press . (This option allows another language to be
toggled easily from the front panel (ex. Spanish as a second language.)).
Press to scroll to choice Non-CE or CE and press .
Press to scroll to choice Gas or Electric and press .
Press to scroll choices: the choices are: Gas-KJ3/CF-FULL, 118G/D63 FULL, H55
FULL, H55 SPLIT, MJ45 FULL, MJ45 SPLIT, HV75 FULL, HV105 FULL, 114/HD50
FULL, HD60 FULL, HD65 FULL D80 FULL, 11814 FULL and MJ35 FULL, . Electric-
118E/RE80 FULL, FPRE117 FULL, FPRE117 SPLIT, FPRE114 FULL and FPRE114
SPLIT, 11817 FULL, FPRE122 FULL, FPRE122 SPLIT FPC128 FULL, FPC128 SPLIT
and FPC136 FULL. With the vat size of the fryer controlled by the Controller displayed,
press .
Sets sound level for Controller. Enter level, 1-9 (0=Lowest/ 9=Loudest). Press .
Press to scroll choices: F for Fahrenheit; C for Celsius. Press .
Use numbered buttons to change default setting (use 10 for 0). Press . (This is the
temperature for the fryer to exit the melt cycle.) Default is 100F (38C).
Use numbered buttons to change default setting (use 10 for 0). Press . (This is the
temperature during setback or idle mode.) Default is 250F (121C).
Press to scroll choices JIB, Bulk-RTI, Bulk-F (Frontline) or None. Press .
All fryers except OCF should be set to NONE.
Press to scroll choices JIB, Bulk-RTI, Bulk-F (Frontline) or None. Press .
All fryers except OCF should be set to NONE.
Press to scroll choices YES and NO. (This is if a drain switch is installed.) Press .
Press to scroll choices DISABLED and ENABLED. (This is a recovery alarm that
locks out the fryer if the fryer does not heat properly. The default is disabled). Press .
Press button.
None required.
Press .
Use numbered buttons to change time (use 10 for 0). Press .
Press to scroll choices. With the date format displayed, press .
Use numbered buttons to change date (use 10 for 0). Press .
Press button once and press to scroll to System, Time/Date, Filter, E-Log, Change
Password or Edit Alarm Names. With desired choice displayed, press or press the
Scan button once to return the Controller to OFF.
1-4
Action
NOTE:
NOTE: