Mitsubishi MELESEC-ST User Manual page 77

Table of Contents

Advertisement

7 I/O MODULES
7 - 17
2) Load of a lamp
Inrush current 10 times as large as the rated current may flow through the
lamp circuit depending on a load.
[Load of an incandescent bulb]
i
io
3 to 10 times
i
Incandescent bulb
Approx. 0.33 seconds
[Load of a mercury lamp]
i
io
3 times
i
180 to 300
seconds
[Load of a fluorescent]
i
io
5 to 10 times
i
Within 10
seconds
io
i: Inrush current
io: Rated current
io
i: Inrush current
io: Rated current
io
i: Inrush current
io: Rated current
MELSEC-ST
7 - 17

Advertisement