06: Bypass enable/disable when UPS is off
07: Bypass voltage range settings
08: Autonomy limitation settings
20
Parameter 3:
Enable or disable
Bypass function. You may choose
the following two options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
Parameter 2&3:
Set the acceptable
high voltage point and acceptable
low voltage point for Bypass mode
by pressing the Down key or Up
key.
HLS:
Bypass high voltage point
-> 230-264: setting the high
voltage point in parameter 3
from 230Vac to 264Vac. (Default:
264Vac)
LLS:
Bypass low voltage point
-> 170-220: setting the low voltage
point in parameter 3 from 170Vac
to 220Vac. (Default: 170Vac)
Parameter 3:
Set up backup time
on battery mode for general
outlets.
0-999:
setting the backup time in
minutes from 0-999 for general
outlets on battery mode.
0:
When setting as "0", the backup
time will be only 10 seconds.
999:
When setting as "999",
the backup time setting will be
disabled. (Default)
5.6

Operating Mode Description

Operating
Description
mode
When the input voltage
is within acceptable
range, the UPS will
Online
provide pure and
stable AC power to the
mode
output. The UPS will
also charge the battery
in the on-line mode.
Energy saving mode:
When the input voltage
is within voltage
ECO mode
regulation range,
the UPS will bypass
voltage to output for
energy saving.
When input frequency
is within 40 Hz to 70
Hz, the UPS can be set
Frequency
at a constant output
Converter
frequency, 50 Hz or 60
mode
Hz. The UPS will still
charge battery under
this mode.
LCD display
21