The UPS is overloaded.
The UPS is overloaded.
The icon
Devices connected to
the UPS are fed directly
and
is
by the electrical net-
flashing on LCD
work via bypass.
display and alarm
is sounding twice
every second.
After repetitive
overloads, the UPS is
locked in the Bypass
mode. Connected
devices are fed directly
by the mains.
Fault code is shown
as 43 and The icon
The UPS shut down
automatically because
is lighting on LCD
of overload at the UPS
display and alarm
output.
is continuously
sounding.
Fault code is shown
as 14 and the icon
The UPS shut down
automatically because
is lighting on LCD
short circuit occurs on
display and alarm
the UPS output.
is continuously
sounding.
26
Remove excess
loads from UPS
output.
Remove excess
loads from UPS
output.
Remove excess
loads from UPS
output first.
Then shut down
the UPS and
restart it.
Remove excess
loads from the
UPS.
Check output
wiring and
if connected
devices are in
short circuit
status.
A UPS internal fault has
Fault code
occurred. There are two
is shown as
possible results:
01, 02, 03,
1. The load is still supplied,
04, 11, 12, 13
but directly from AC power
and 41 on
via bypass.
LCD display
2. The load is no longer
and alarm is
supplied by power.
continuously
sounding.
Battery
Batteries are not fully
backup time
charged.
is shorter
than nominal
value.
Battery defects
Disposal of Old Electrical & Electronic Equipment
(Applicable in the European Union and other European countries
with separate collection systems)
This symbol on the product or on its packaging indicates that this product shall
not be treated as household waste.
Instead it shall be handed over to the applicable collection point for the
recycling of electrical and electronic equipment.
By ensuring this product is disposed of correctly, you will help prevent potential
negative consequences for the environment and human health, which could
otherwise be caused by inappropriate waste handling of this product.
The recycling of materials will help to conserve natural resources.
Contact the
service center.
Charge the
batteries for at
least 5 hours
and then check
capacity. If the
problem still
persists, contact
the service center.
Change battery.