Mounting the C200HW-CORT21

2-2

Mounting the C200HW-CORT21

Limitations
2-3

Network cabling

The C200HW-CORT21 can be mounted to the CPU Rack or Expansion I/O
Rack of any CS1, C200HX, -HG, or -HE PLC. Refer to the PLC's Operation
Manuals for details on mounting Units.
There are some limitations on mounting the Unit.
The current consumption of all Units mounted on one backplane should
not exceed the maximum output of the power supply. The C200HW-
CORT21 consumes up to 250 mA from the 5V supply. Verify the
characteristics of all other Units on their respective Instruction Sheets.
The C200HW-CORT21 is a Special I/O Unit. It can be mounted in any
slot in the backplane of a CPU Rack or Expansion I/O Rack as long as
its Unit number is not the same as the Unit number of another Special
I/O Unit within the system.
The maximum number of Special I/O Units that can be mounted depends
on the PLC CPU type.
For details on CS1-series PLC compatibility, see Appendix A.
CPU Unit models
C200HE,
C200HG-CPU3 -E/CPU4 -E,
C200HX-CPU3 -E/CPU4 -E
C200HG-CPU5 -E/CPU6 -E,
C200HX-CPU5 -E/CPU6 -E/CPU8 -ZE
CS1-series
All devices are connected in a bus structure (i.e. line). The wiring topology of
a CAN network should be as close as possible to a single line structure in
order to avoid cable-reflected waves. Stub-lines should be kept as short as
possible and must be less than 30 cm at the highest baud rate (1 Mbit/s).
Section 2-2
Max. number of
Special I/O Units
10
16
27