Overall Specifications - Omron C200HW-CORT21 Operation Manual

Table of Contents

Advertisement

Overall Specifications

1-1

Overall Specifications

Model code
Host PLC system
Maximum number of Units
per PLC system.
Unit mounting position
Current consumption
Network power supply
Weight
Storage temperature
Operating temperature
Operating humidity
Conformance to EMC- and
environmental standards
Switch Settings
Indicators
No. of IR words
No. of DM settings
Amount of I/O data
per Unit
Message communications
Bus connector
Node address
Baud rate
CAN interface
16
C200HW-CORT21
C200HE, C200HG, C200HX, CS1
C200HE
C200HG-CPU3 -E/CPU4 -E
C200HX-CPU3 -E/CPU4 -E
All others
CPU Rack or Expansion I/O Rack
Unit cannot be mounted to SYSMAC BUS Slave Racks.
Internal I/O power supply: 250 mA at 5V DC max. (from PLC)
Network power supply:
24 V DC ± 10%
250 g
-20 to +75°C
0 to +55°C
10% to 90% (non-condensing)
EN50081-2
EN61131-2
Special I/O Unit number (0 ~ F) by rotary switch
Network baud rate (10 kbit/s ~ 1000 kbit/s) by 3 DIP-switches
Unit status:
RUN (green LED), ERR (red LED)
Network status: 2 x 7-segment display
PLC → Unit:
3 words
Unit → PLC:
5 words
20 words
CAN data is transmitted via IOWR PLC instruction and received CAN
messages are transferred during the I/O refresh. Max number of words
transferred during I/O refresh is 91 words.
Via IOWR / IORD instructions
5-pin male open style connector
N.A.
10, 20, 50, 125, 250, 500, 800, 1000 kbit/s
(note: Refer to section 3-1-1 for the configuration of any arbitrary baud rate via
the DM settings.)
ISO 11898, High Speed CAN.
10
16
45 mA max. (from communications connector)
Section 1-1