Applying Power; Assigning The Module - Kantech KT-315 Installation Manual

Door controller
Table of Contents

Advertisement

1. Connect the four Combus wires to the KT-PC4108. Connect the Red, Black, Yellow and Green Combus wires to the RED,
BLK, YEL and GRN terminals, respectively.
2. Complete all zone wiring to the zone input terminals (Z1-Z8).
3. Connect the external tamper switch, if used.
NOTE:
Consult the wiring diagram above for further information.

Applying Power

After wiring is completed, apply power to the controller. Connect the battery leads to the battery, then connect the AC
transformer.
NOTE:
Do not connect the power until all wiring is completed.

Assigning the Module

Once all wiring is completed, the module must be assigned to the system. To assign the module, perform the following steps:
1. Establish communication between EntraPass 5.01 or higher and the controller.
2. Remove the tamper switch wire (or only the wire if tamper switch is not used). If there is no connection to the TAM input, use
the Tamper Switch button to generate an event.
3. An event will be displayed on the EntraPass workstation Desktop Message screen, indicating the module's serial number,
type and the controller to which it is connected.
4. From the software, select the functionality of the module and enter the serial number in the appropriate field (see your
software reference manual under controller definition -- Assigning modules for more details).
NOTE:
Do not forget to reconnect the tamper switch (or the wire, if there is no tamper switch).