You agree unconditionally to be bound by the terms of this EULA, even if this EULA is deemed to be a modification of any previous arrangement or contract. If You do not agree to the terms of this EULA, KANTECH is unwilling to license the SOFTWARE PRODUCT to You, and You have no right to use it. SOFTWARE PRODUCT LICENSE a - The SOFTWARE PRODUCT is protected by copyright laws and international copyright treaties, as well as other intellectual property laws and treaties.
Page 4
PRODUCT is an upgrade, any transfer must also include all prior versions of the SOFTWARE PRODUCT. f - Termination - Without prejudice to any other rights, KANTECH may terminate this EULA if You fail to comply with the terms and conditions of this EULA. In such event, You must destroy all copies of the SOFTWARE PRODUCT and all of its component parts.
Page 5
BE UNINTERRUPTED OR ERROR-FREE. b - CHANGES IN OPERATING ENVIRONMENT KANTECH shall not be responsible for problems caused by changes in the operating characteristics of the HARDWARE, or for problems in the interaction of the SOFTWARE PRODUCT with non-KANTECH SOFTWARE or HARDWARE PRODUCTS.
WARNING: DO NOT LOOK DIRECTLY AT LED WITH UNSHIELED EYES: DAMAGE TO RETINA MAY OCCUR. The KT-1 One-Door Controller shall be installed and used within an environment that provides the pollution degree max 2, and over voltages category II NON HAZARDOUS LOCATIONS, INDOOR only.
Page 8
3 - If during the installation a knockout on the cabinet is removed, it is the installer's responsibility to ensure that the same degree of protection for the cabinet is provided by the use of bushings, fittings, adequate sealant, etc. 4 - If a metallic cabinet is used, the cabinet must be secured to the building struc- ture before operation.
Page 9
Technical Support For technical assistance with this and other Kantech products, contact technical sup- port, Monday to Friday. See the following table for the technical support phone numbers. Country/Region Phone Numbers Support Hours E-mail North America Toll Free +1 888 222 1560 (GMT -05:00)
Overview of Features The KT-1 One-Door Controller is designed to meet the highest standards of access control and point monitoring applications. The KT-1 is available in two configurations: • KT-1 (single gang mount) • KT-1-PCB More information is available near the end of this guide on expansion kits and related items.
Page 12
IP Communication Configuration Web Configuration Page: The Web Configuration Page can be used to verify and configure the IP settings of the KT-1. Refer to the System Architecture section of this guide for further details. KT-Finder: The KT-Finder is a stand-alone application that can be used to verify and configure the IP settings of the KT-1.
Page 13
IP Connectivity With or Without PoE/PoE+ When used with EntraPass Special Edition, Global Edition and Multi-Site Gateway, the KT-1 can gather its configuration through an IP connection over the LAN (Local Area Network) and over the Internet for a WAN (Wide Area Network), (WAN con- figuration not recommended with Global Edition).
Page 14
15 seconds to 140 seconds. The loss of communication notification will occur when the network pulse time has elapsed twice plus 15 seconds. Note: The KT-1 has been tested by UL with the PoE/PoE+ models Phihong POE36U- 1AT-R and/or the POE125U-4-HP-R. These devices shall be used in conjunction with UL listed transient protectors.
Page 15
Note: Supervision is only provided to detect short-circuit fault, not open-circuit fault. Relay Outputs The KT-1 has 2 open collector onboard switch to ground relay outputs. The KT-1-PCB has 2 form C relays. Reader Outputs There are 4 different possible open collector, switch to ground, outputs. Reader out- puts are used to give user visual and/or audible feedback on the ongoing access events.
Page 16
IP (ETHERNET) or RS-485 (COM1). Downloadable Firmware The firmware program can be downloaded from any EntraPass workstation to the KT-1. It is stored in the controller’s flash memory, and is upgraded without having to change any parts. Trouble and Reporting The KT-1 continuously monitors its power and reports low and critical power issues.
LED Patterns Visual Status Indicators (LEDs) The front cover of the KT-1 controller has multiple LED status indicators, which are used for such activities as troubleshooting, network activity, power status and out- puts. The LED status indicators, as illustrated on the cover diagram below, are as follows: •...
Page 24
Heartbeat LED Patterns Communication status and other vital controller parameters can be obtained from heartbeat LED patterns located in the Kantech shield on the cover. This information is particularly useful when connecting the controller to the rest of the EntraPass sys- tem.
Page 25
(14°F to 131°F) Environmental Class II Humidity Level 93% max. (relative humidity non-condensing) From wall surface (Width x Height x Thickness) 3.4” x 5.125” Cabinet dimensions: KT-1 x 1.81” (2.4” overall thickness) Cabinet dimensions: KT-1- 4.78'' x 5.436'' x 1.863'' Weight: KT-1 10.75 ounces (305g)
Page 26
AES Encryption AES NIST Validation of certificate No. 3092 *Note: The KT-1 has been tested by UL with the PoE/PoE+ modles Phihong POE36U-1AT-R and/or the POE125U-4-HP-R. These devices shall be used in con- junction with UL listed Transient protectors. Other compatible PoE/PoE+ con- figurations may be possible.
Installation, Connection & Power Overview Installation of the KT-1 varies with the type of unit: KT-1 or KT-1-PCB. Installation is also dependent on the selection of the 12 V or PoE/PoE+ as the power source (see Powering the KT-1 later in this section for more details).
Page 28
KT-1 Installation 1 - Complete each of the required connections on the small board (B) which mounts on the wall-plate. 2 - Install the wall-plate (A) to the wall using the two Phillips screws provided. 3 - Clip board (B) on the wall plate (A).
Page 29
Connect the ground wire to the green quick- connect terminal. Make an earth ground connection to the cabinet of the KT-1 con- troller as per the requirements of your local electrical code. Wire the E-GND ter- minal on the KT-1 printed circuit board directly to that connection point.
Page 30
DC powered locking devices such as electromechanical strikes and can be configured to operate fail-safe or fail-secure (normal or reverse action). Note: If required, the KT-1 can provide galvanically isolated output(s) by pro- gramming any of the relays (KT-1-PCB only).
Page 31
Connect devices to inputs 1 to 4. Resistors for all inputs are 5.6K ohm (if selected). The KT-1 has an on-board capability of monitoring 4 input points. Each onboard input is supervised with or without end-of-line resistors (5.6K ohm). The maximum distance of one line is 600 m (2,000 ft) with AWG #22 in a single or double EOL con- figuration.
Page 33
Connecting Reader Units The KT-1 provides 12 VDC power for card readers. Up to 2 readers can be con- nected to a KT-1. The distance between the readers and the KT-1 varies by reader type, please refer to the documentation provided with the reader. Auxiliary outputs provide visual and/or audible access operation feedback at the controlled door.
Page 34
RELAY1 and RELAY2. These relays are rated at 3 Amps, 30 VAC/VDC, 0.6 power factor. Relay Controlled Outputs for the KT-1 Relay Controlled Outputs for KT-1-PCB Auxiliary Outputs Connect auxiliary outputs to readers and local warning devices. Auxiliary outputs are used for visual and audible signals. They can be activated according to input con-...
Page 35
9600 or 19200 Bauds. Varying the network speed does not notice- ably change the operation speed of the system. Note 1: Connecting several KT-1 at a single point is not recommended, neither are splitters or spider web (star) networks.
Page 37
Use PoE/PoE+ Phihong models POE125U-4-HP-R or POE36U-1AT-R. AC trouble output from KT-PS4085 power supply shall be con- nected to one of the available inputs on KT-1 for transmission of AC loss event to the monitoring console.
Page 38
Reset & Configuration One Button The One Button is used in the configuration of the KT-1 controller. It is located on the lower front of the KT-1, where the Kantech Shield is placed. Placing a finger over the imprint of the shield activates various functionalities of the controller.
Page 39
A reset of the system is possible using the reset button located on the main board. The main board is accessed by removing the front cover of the KT-1. The reset but- ton is on the bottom right side and is accompanied by a legend detailing the reset options.
Page 40
Reset Chart The following chart indicates reset types, with expanded descriptions below: Forced Default Soft Hard Factory Default DHCP Static Press and release Initiation Hold 3 seconds until 5 beeps within 2 seconds Action 1 Hit 2 Hits 3 Hits Confirmation Hold 3 seconds until 5 beeps See LED Patterns...
Page 41
The KT-1 default initialization or Factory Default DHCP is done at Kantech. The fol- lowing steps should be followed only if: • You want to configure the KT-1 with the KT-Finder. (Refer to the section on con- figuring the KT-Finder, in this guide).
Page 42
1 - Determine your connection to the KT-1 and choose the appropriate network cable that you need. 2 - Make sure the KT-1 is in Forced Default Static mode before starting the con- figuration. Verify the heartbeat patterns to determine the status. See the Power LED Status Indicator table for details.
Page 43
6 - Enter a Port (UDP only). 7 - Click on Save configuration to KT-1. 8 - When you go to the site with the configured KT-1, you will have to enter the same details into the EntraPass workstation. Configuring the KT-1 with the KT-Finder The KT-Finder is an application used to configure the KT-1 over the local area net- work (LAN) or the wide area network (WAN).
Page 44
• Available as a free download from http://www.kantech.com 1 - Quit all EntraPass applications. 2 - Make sure the KT-1 is in Factory Default DHCP mode. See the Power LED Status Indicator table for details. 3 - Start the KT-Finder.
Page 46
Description KT-1 Models KT-1 One-Door IP controller Single Gang Mount KT-1-M One KT-1-PCB, IP controller PCB with metal cabinet (No P/S, No BAT) One-Door IP Controller PCB including connector board (Compatible with KT- KT-1-PCB 1-CAB-M or P) KT-1-CVR Black replacement cover for KT-1 including back box...
Standby power: Level 1 (when no standby power is provided) and level IV (4 hours, when using KT- PS485) Note: If KT-1 is used in a single gang configuration, powered by an external, separately listed power sup- ply or PoE/PoE+ switch the performance levels remain the same with the exception of the standby time that will be rated Level I (no secondary power source).
Page 48
UL 1076 Compliance Notice • The KT-1 is UL 1076 Listed as a Commercial Proprietary Control Unit Accessory and Proprietary Burg- lar Alarm Unit (Section 83.2), with EntraPass and Redundant Server, alarm system features, KT-300, KT-400 Controllers, Kantech ioProx Proximity readers, and TRex request to exit devices – other sensor devices (temperature, water level, etc.) may be used as long as they are also UL 1076 Listed.
Page 49
• The following Kantech readers have been validated by UL for the UL 1076 Standard: P225W26, P225KPW26, P225XSF, P225KPXSF, P325W26, P325KPW26, P325XSF, P325KPXSF and P600. • All alarms shall be reported and acknowledged in the following priority: Note: To set these priorities, please adjust the Event Parameters, found in EntraPass System •...