Danfoss EM-PMI375 User Manual page 48

Hide thumbs Also See for EM-PMI375:
Table of Contents

Advertisement

User Guide
EM-PMI375
Installation
48 |
©
Danfoss | November 2021
Connecting cable lug
7. Cut piece of shrink tube and shrink it over the cable lug and braid screen as shown in Figure below.
This is done to keep the braid screen in place and for extra insulation.
The shrink tube must be specified for operating temperature range from -40 ºC to 150 ºC.
Self gluing shrink tube is recommended.
Shrink tube
8. Insert the cable through the corresponding hole in the connection box and connect the cable lug to
the connection point. Use spring washer between the cable lug and the connection screw or nut.
Example of the connection is shown in Figure below. Do not tighten the connection at this point to
ensure fitting of the cable gland.
Make sure that there is at least 10 mm air gap between the cable lug and other metallic
structures including the braid of the cable. If the air gap is smaller, use extra insulation
shrink tube to cover the lug.
BC265856307805en-000202

Advertisement

Table of Contents
loading

Table of Contents