1: Nfpa Battery Requirements; 2: Selecting And Locating Batteries - Honeywell Notifier SFP-2402 Instruction Manual

Table of Contents

Advertisement

Calculating the Battery Size
1.
Enter the totals from Table 5.3 on page 46, Calculation Columns 2 and 3 where shown.
2.
Enter the NFPA Standby and Alarm times (refer to 'NFPA Requirements' below).
3.
Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere
hours.
4.
Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH).
5.
Write the ampere hour requirements on the Protected Premises label located inside the cabinet
door.
Secondary Standby Load
(total from Table 5.3 Calculation
Column 3)
[
]
Primary Alarm Load
(total from Table 5.3 Calculation
Column 2)
[
]
Sum of Standby and Alarm Ampere Hours
Multiply by the Derating Factor
Battery Size, Total Ampere Hours Required
Table 5.4 Total Secondary Power Requirements at 24 VDC
5.4.1 NFPA Battery Requirements
NFPA 72 Local, Central and Proprietary Fire Alarm Systems require 24 hours of standby
power followed by 5 minutes in alarm
NFPA 72 Auxiliary and Remote Station require 60 hours of standby followed by 5 minutes in
alarm. Batteries installed in a system powered by a generator need to provide at least 4 hours
of standby power
5.4.2 Selecting and Locating Batteries
Select batteries that meet or exceed the total ampere hours calculated in Table 5.4 . The control
panel can charge batteries in the 7 AH to 18 AH range. The control panel cabinet is capable of
housing batteries up to 7 AH. Batteries larger than 7 AH require the BB-17F or other UL listed
external battery cabinet.
SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014
Required Standby Time
(24 or 60 hours)
X[
]
Required Alarm Time
(for 5 min., enter 0.084,
for 10 min., enter 0.168)
X[
]
Power Supply Calculations
=
AH
=
AH
=
AH
X 1.2
=
AH
47

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier sfp-2404Notifier sfp-2402eNotifier sfp-2404e

Table of Contents