SFP-2402/SFP-2404 & SFP-2402E/SFP-2404E Fire Alarm Control Panels
NORMAL - Only the GREEN AC POWER LED is on.
All other LEDs are off.
WHEN AUDIBLE DEVICES ARE SOUNDING -
FOR AN ALARM
1. Evacuate the protected area
2. Notify the monitoring service and/or the Fire Department immediately. Tell them briefly what happened and what your current status is.
Phones: ________________________________________
3. If the Fire Department is responding, be prepared to provide directions to arriving firefighters.
FOR TROUBLE ONLY
1. Notify the monitoring service and/or Fire department if this panel is connected to either one, and tell them what is happening.
2. Silence audible devices by unlocking and opening the panel and pressing the ACKNOWLEDGE key for a minimum of one second. The
yellow SYSTEM TROUBLE LED will remain on. Contact authorized service personnel immediately! (See Below).
DO NOT ALLOW TROUBLE CONDITIONS TO REMAIN LOGGED IN THE SYSTEM. THE PROTECTION THE
SYSTEM OFFERS HAS BEEN COMPROMISED OR ELIMINATED, WHEN A TROUBLE CONDITION EXISTS.
To return to normal after an alarm
1. Do not enter the protected area until safe to do so.
2. Clear all initiating devices. Smoke detectors will not reset if there is
still smoke in the area.
3. Reset the control panel (PRESS the RESET key.)
Power failure or brownout
If AC power drops too low or fails, the AC POWER LED will go out, the
SYSTEM TROUBLE LED will turn on, the POWER TROUBLE LED will
turn on, and the panel buzzer and any other audible trouble devices will
sound. Contact authorized service personnel immediately. See below.
Manual activation (Fire Drill or otherwise)
In the event of trouble, contact the
local Notifier Service Representative
Name: _____________________________________
Company: __________________________________
Address: ___________________________________
Telephone Number: __________________________
Operating Instructions
Fire Department
WARNING!
PANEL KEY - The key to open the panel can be found at the following
location:
________________________________________________________
_____________________________________________
Monitoring Service
Notification Appliance Circuits (NACs) can be activated by activating a
manual pull station.
NOTE: You may want to disconnect the municipal box by
sliding the DISCONNECT switch, located on the 4XTM
module, to its disconnect position (to the right). If a DACT is
connected, notify the monitoring service before conducting
any fire drills or tests.
Alarm Silencing
Notification Appliance Circuits may be silenced by pressing the
ACKNOWLEDGE key and then the ALARM SILENCE key. The ALARM
SILENCED LED will turn on. Subsequent alarms will reactivate circuits.
Press the RESET key to clear the "silenced" condition.
NOTE: Notification Appliance Circuits may be programmed
as nonsilenceable. Also, Signal Silence Inhibit, if enabled,
will prevent silencing of NACs for one minute after an alarm
(see manual).
To test the lamps and piezo sounder
Press and release the RESET key and check all LEDs. Every LED
should be on and the piezo should sound.
For more information, refer to the SFP-2402/E & SFP-2404/E Manual,
Document #51898. It is kept in the following location:
_______________________________________________________
THIS SHEET SHALL BE FRAMED ADJACENT TO THE
CONTROL PANEL
Document #51913
Rev. B
1/25/05
ECN 04-724