Optional Modules and Accessories
4XLM LED Interface Module (SFP-2404 only)
The LED Interface Module supports the RZA-4X Remote Annunciator module. Annunciator
wiring is supervised for open conditions by this module. The 4XLM mounts to the SFP-2404 main
circuit board option module connectors J3 and J5 only.
RZA-4X Remote Annunciator (SFP-2404 only)
The Remote Annunciator mounts on a standard single-gang electrical box and provides LED
indication of the following:
Alarm Zone 1 (red LED)
Alarm Zone 2 (red LED)
Alarm Zone 3 (red LED)
Alarm Zone 4 (red LED)
System Trouble (yellow LED)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is supervised for
open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in
paper labels permit an easy change of zone information.
NOTE: The RZA-4X Remote Annunciator requires the use of the LED Interface Module (4XLM).
4XZM Zone Relay Module (SFP-2404 only)
The Zone Relay Module provides Form-C relay contacts for the following:
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 4
System Alarm
System Trouble
As a jumper option, the first four relays described above can be made silenceable. The 4XZM
mounts to the SFP-2404 main circuit board, occupying one of the two sets of option module
connectors.
Dress Panel DP-3-B
A dress panel DP-3-B is optional. The dress panel restricts access to the system wiring while
allowing access to the membrane switch panel.
Battery Box
The BB-17 battery box may be used to house two batteries greater than 7 Amp Hour to a maximum
of 18 Amp Hour. The battery box mounts directly below the control panel cabinet, centered to the
main circuit board. The BB-17 is provided with knockouts.
411 and 411UD Digital Alarm Communicator/Transmitter
The three input/channel 411 and the four input/channel 411UD are dual line, digital alarm
communicator/transmitters which can be used as slave communicators with the SFP-2404 FACP.
The inputs/channels are compatible with normally open relay contacts, require ELRs (End-of-Line
Resistors), are supervised and are fully programmable. The communicators interface with the
public switched telephone network and are compatible with most central station receivers. Power
supplied must be 12 or 24 volts, filtered and nonresettable. The communicators are mounted in a
small metal enclosure, providing a variety of mounting options. Refer to the 411 or 411UD manual
for additional information.
SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014
Product Description
15