Honeywell Notifier SFP-2402 Instruction Manual page 9

Table of Contents

Advertisement

SFP-2404 Four Zone Main Circuit Board
IDC (4.7 K:, ½ watt ELR) TB3 (supervised, power-limited)
NAC (4.7K:, ½ watt ELR)
TB2 2.5A max. per NAC
(supervised, power-limited)
NAC 2 B-
NAC 2 B+
NAC 1 B-
NAC 1 B+
24 VDC Special Application
Power TB1
500 mA per circuit
(nonsupervised, power-
limited)
- Reset
+ Reset
- Nonreset
+Nonreset
+
-
+
-
Nonreset Reset
J9
J7
J7 Transformer
Connector
J9 Transformer
(optional)
120 VAC, 2.3A or
220/240 VAC, 1.15A
Hot
Neutral
Earth
(supervised,
nonpower-limited)
SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014
Zone 4 B-
Zone 4 B+
Zone 3 B-
Zone 3 B+
Zone 2 B-
Zone 2 B+
Zone 1 B-
Zone 1 B+
B+
B-
B+
B-
B+ B-
B+
B-
ZONE 1 ZONE 2
NAC 1
NAC 2
Converter Module
ZONE 1
FIRE ALARM
SUPERVISORY
ZONE 2
FIRE ALARM
SUPERVISORY
ZONE 3
FIRE ALARM
SUPERVISORY
ZONE 4
FIRE ALARM
SUPERVISORY
NAC
NAC
ZONE
AC
DISABLE
DISABLE
FAULT
POWER
ALARM
ACK
SILENCE
ZONE
ENABLE/DISABLE
1
2
TB8
BATTERY
HOT NEUT EARTH
J8 Battery
Connector
(supervised,
nonpower-limited)
18 Amp Hour max.
B+
B-
B+
B-
C TRBL NORM
ZONE 3 ZONE 4
TROUBLE
CLASS A
CONVERTER
J1
Class A
TROUBLE
MAINTENANCE
TROUBLE
MAINTENANCE
TROUBLE
MAINTENANCE
TROUBLE
MAINTENANCE
ALARM
POWER
WALK
SYSTEM
SILENCE
TROUBLE
TEST
TROUBLE
WALK
RESET
TEST
3
4
JP1
JP2
EARTH BATT CHG
J8
SW1
SW2 SW3
Module Placement Supervision (if installed)
JP1 - cut to supervise module on J3 & J5
JP2 - cut to supervise module on J4 and J6
Charger Fault LED
Battery Fault LED
Earth Fault LED
Trouble Relay TB5 (fail-safe)
2A @ 30 VDC (nonsupervised)
Common
Trouble (Normally Open)
Normal (Normally Closed)
Alarm Relay TB6
2A @ 30 VDC
(nonsupervised)
Common
Normally Closed
Normally Open
Supv. Relay TB7
2A @ 30 VDC
(nonsupervised)
Common
Normally Closed
Normally Open
C
NC NO
C
NC NO
ALARM
SUPV
JP3
JP3 - Cut to disable
Ground Fault
J3
detection (only with
approval of AHJ)
J5
J3 and J5
Option Module
Connectors
J4
J4 and J6
J6
Option Module
Connectors
SW1, SW2 and SW3
Programming DIP Switches
Note: Factory-installed cover
removed for illustration purposes
only!!
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier sfp-2404Notifier sfp-2402eNotifier sfp-2404e

Table of Contents