To connect wiring:
For Incoming 120VAC and 24VDC for accessories
1 .
For 20 - 10 AWG wire
2 .
Strip end of wire 1/4 inch
3 .
Insert wire into appropriate position as shown
and use flat head screw driver to secure
Error Code
Short Circuit
Temperature Trip
Over Voltage
Under Voltage
Aux 1 Stuck
Aux 2 Stuck
Aux 3 Stuck
Comm Error
Presence Detect
Drive Disabled
16
D6011/D6051 Double Unit Series (Pull Side) Power Operator
Factory Pre-Wiring of Connections and Incoming Wiring
Controller Error Codes
A short was sensed on the motor outputs
Power module reached 200°F or greater (too much load in too hot ambient
condition)
Line Voltage has reached 145VAC or greater
Line Voltage has dropped below 80VAC
Activation device connected to Aux 1 is sending constant signal
Activation device connected to Aux 2 is sending constant signal
Activation device connected to Aux 3 is sending constant signal
No communication between top and bottom controller boards . Boards not
functioning properly
Device connected to Presence Detect and was activated
Selector mode switch on end cap closest to latch is in "OFF" position
For Low Voltage / Dry Contacts on Inverter
1 .
For 24 - 16AWG wire
2 .
Strip end of wire 3/8 inch
3 .
Use flat blade screw driver to push down on
white button above desired location, insert
wire, release button. Pull on wire to confirm
installed properly .
Description
Copyright © 2019-2020, ASSA ABLOY Accessories and Door Controls Group, Inc. All rights reserved. Reproduction in whole
or in part without the express written permission of ASSA ABLOY Accessories and Door Controls Group, Inc. is prohibited.
80-9360-1029-020 Rev 5 11/20