IMPORTANT: Owner's should check pilot flame pattern and burner flame pattern often.
Incorrect flame patterns indicate the need for cleaning (see Care and Maintenance,
page 23) or service.
WARNING: Only a qualified service person should service and
repair heater. This includes maintenance requiring replacement or
alteration of components.
Figure 24 shows a correct pilot flame pattern.
Figure 25 shows an incorrect pilot flame pat-
tern. The incorrect pilot flame is not touching
the thermocouple. This will cause the ther-
mocouple to cool, which shuts the heater off.
If pilot flame pattern is incorrect, as shown
in Figure 25
• turn heater off (see To Turn Off Gas to Ap-
pliance, page 19)
• see Troubleshooting pages 25 through 28.
WARNING: If yellow tipping
occurs, your heater could pro-
duce increased levels of carbon
monoxide. If the burner flame
pattern shows yellow tipping,
follow instructions at bottom of
this page.
Figure 26 shows a correct burner flame pattern. Figure 27 shows an incorrect burner flame
pattern. If burner flame pattern is incorrect then:
• turn heater off (see To Turn Off Gas to Appliance, page 19).
• see Troubleshooting pages 25 through 28.
Approx. 3"-6" Above Top of Logs
Figure 26 - Correct Burner Flame Pattern
More Than 8" Above Top of Logs
Air is drawn into the burner through the holes in the fitting at the entrance to the burner. These
holes may become blocked with dust or lint. Periodically inspect these holes for any blockage
and clean as necessary. Blocked air holes will create soot.
22

INSPECTING BURNERS

PILOT FLAME PATTERN
BURNER FLAME PATTERN
BURNER PRIMARY AIR HOLES
www.usaprocom.com
Notice: Do not mistake orange flames with
yellow tipping. Dirt or other fine particles enter
the heater and burn causing brief patches of
orange flame.
Natural Gas
Shown
NG
3-3.5" WC
Figure 24 - Correct Pilot Flame Pattern
(Natural Gas shown)
Natural Gas
Shown
NG
3-3.5" WC
Approx. 3"-6" Above Top of Logs
Figure 25 - Incorrect Pilot Flame Pattern
(Natural Gas shown)
More Than 8" Above Top of Logs
Figure 27 - Incorrect Burner Flame
Pattern
LP
8-11" WC
LP
8-11" WC
200228-01A