Drive Specifications - Allen-Bradley Ultra1500 Quick Start Manual

Digital drives
Hide thumbs Also See for Ultra1500:
Table of Contents

Advertisement

Drive Specifications

Drive
Weight
Temperature
Operating Shock,
and Vibration
Short Circuit Current Rating with
No Fuse Restrictions
Short Circuit Current Rating with
Fuse Restrictions
Motor Overload Protection
Symbols Used on Drive
Certification and Compliance
Main Input Power
Nominal Input Voltage (V
Input Current (A
)
rms
Maximum Inrush Current (0-peak)
Maximum Power Cycles/Minute
DC Bus Discharge Time
Control Input Power
2,3
Input Voltage (V
)
rms
Input Current (A
)
rms
Maximum Inrush Current (0-peak)
Motor Output
Continuous Output Current (0-peak)
Intermittent Output Current (0-peak) 3.4A
Continuous Output Power @ 240V
Power Dissipation
Maximum Power Dissipation
1 Refer to www.ab.com/certification/ce/doc for more information.
2 Nominal values are listed. Absolute range is 180 to 264 V
3 The AC input voltage between any two input power pins (L1, L2, L3, L1C, L2C, and CHASSIS) must not exceed this rating. This note also applies to the
CHASSIS ground connection, which implies that transformer secondaries must be grounded.
4 Maximum Power Dissipation includes dissipative power of drive plus the Continuous Shunt Power rating of the drive's internal shunt.
2092-DA1
0.9 kg (1.98 lbs)
0° C to 50° C (32° F to 122° F)
15 G, Half Sine, 11 ms
5 – 500 Hz @ 2.5 G, 0.381 mm (0.015 in.) maximum displacement
Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 240 Volts maximum.
Suitable for use on a circuit capable of delivering not more than 200,000 rms
symmetrical amperes, 240 Volts maximum, when protected by high interrupt
capacity, current limiting fuses UL198C (Class CC, G, J, L, R, T).
Utilizes solid state motor overload protection which operates:
• within 8 minutes at 200% overload.
• within 20 seconds at 600% overload
Protective ground conductor terminal
1
®
UL
listed to U.S. and Canadian safety standards (UL 508C File E145959)
CE and C-Tick marked for all applicable directives
2,3
200-240V, 1 phase, 50 or 60 Hz
rms)
3.3A
200A
1 power cycle/2 minute interval
3 minutes after removal of main AC power
200-240V, 1 phase, 50/60 Hz
2.0A
75A
1.4A
400W
ac
50W
rms
2092-DA2
2092-DA3
1.2 kg (2.65 lbs)
5.5A
8.0A
2.4A
4.7A
7.2A
11.3A
650W
1000W
50W
50W +30W
.
Publication 2092-QS001D-EN-P — July 2005
Ultra1500 Digital Drives Quick Start
2092-DA4
2.1 kg (4.63 lbs)
200- 240V, 3 phase, 50 or 60 Hz
11.0A
10.7A
24.8A
3000W
4
100W+50W
13
2092-DA5
15.0A
16.4A
43.4A
4000W
4
4
150W+70W

Advertisement

Table of Contents
loading

This manual is also suitable for:

2092-da12092-da22092-da32092-da42092-da5