11.
TROUBLESHOOTING
Table 11.1 Error Code List for the AnUCPU, A2US(H)CPU, A2ASCPU and A2USH board (Continue)
Error
Error Massage
Code
(D9008)
"SP.UNIT
44
LAY.ERR."
Detailed
Error
CPU
Code
States
(D9091)
441
STOP
A special function module is assigned
as an I/O module, or vice versa, in the
I/O assignment using parameters from
the peripheral device.
442
There are 9 or more special function
modules (except the interrupt module)
which can execute interruption to the CPU
module loaded.
443
There are 2 or more data link modules
loaded.
444
There are 7 or more modules such as
a computer link module loaded to one
CPU module.
445
There are 2 or more interrupt modules
loaded.
446
Modules assigned by parameters for
MNT/MINI automatic refresh from the
peripheral device do not conform with
the types of station modules actually
linked.
447
The number of modules of I/O
assignment registration (number of
loaded modules) per one CPU module
for the special function modules which
can use dedicated instructions is
larger than the specified limit. (Total of
the number of computers shown
below is larger than 1344.)
+
448*
(1) Five or more network modules
have been installed.
(2) A total of five or more of network
modules and data link modules
have been installed.
Error and Cause
(AD59
5)
(AD57(S1)/AD58
8)
(AJ71C24(S3/S6/S8)
10)
(AJ7IUC24
10)
(AJ71C21(S1) (S2)
29)
((AJ71PT32(S3) in extension
mode
125)
Total
1344
11 - 18
Corrective Action
Execute I/O assignment again using
parameters from the peripheral device
according to the loading status of special
function modules.
Reduce the special function modules (except
the interrupt module) which can execute
interrupt start to 8 or less.
Reduce the data link modules to 1 or less.
Reduce the computer link modules to 6 or
less.
Reduce the interrupt modules to 1 or less.
Perform again module assignment for
MNT/MINI automatic refresh with
parameters according to actually linked
station modules.
Reduce the number of loaded special
function modules.
Make the total of the installed network
modules and data link modules four or
less.