Table 6-2: LOI Button Operation
Button
Left
Right
Figure 6-1: LOI Menu
6.3
Switch HART Revision mode
If the HART configuration tool is not capable of communicating with HART
Revision 7, the Rosemount 2051 will load a generic menu with limited
capability. The following procedures will switch the HART Revision mode
from the generic menu:
Procedure
Navigate to Manual Setup → Device Information → Identification →
Message
a) To change to HART Revision 5, Enter: HART5 in the Message field.
b) To change to HART Revision 7, Enter: HART7 in the Message field.
Quick Start Guide
No
Yes
Quick Start Guide
SCROLL
ENTER
Assign PV
HART Revision