F7 Overview connector / Counterpart with description / Scope of delivery
CONNECTOR
V
/V
IN
OUT
RL
USB
RS232
SCOPE OF DELIVERY
QUANTITY
1x device
1x
1x
F8 Charging time
Charging times depend on energy storage, input voltage and the load current.
F9 Reverse polarity / Overcurrent / Short circuit
Reverse polarity:
The device has active reverse polarity protection at the input if the input terminal is connected with reverse
polarity while the device is still switched off (e.g. during commissioning). If the device operates in battery mode
and the input terminals are connected with reverse polarity, no reverse polarity protection is given.
Overcurrent:
If the load current at the output is too high, the device switches it off. For maximally allowed current values
and peak current values refer to chapter D „Technical Data". The status LED indicates the error status by means
of a very rapid flashing sequence. A restart attempt occurs every 10 seconds in normal mode. During battery
mode there is no restart attempt.
Short circuit:
In the event of a short-circuit at the output of the UPS, the output is immediately disconnected (<5 ms). The
status LED indicates the error status by means of a very rapid flashing sequence. A restart attempt occurs every
second in normal mode (non-latch). During battery mode there is no restart attempt. The impact of a short-
circuit to the device depends on length and diameter (impedance) of the output wiring. In case of a short-circuit
directly at the plugs a damage of the device can occur.
Revision 1-5
PART NO.
Würth Elektronik 691325310004
Würth Elektronik 691305140002
Würth Elektronik 61400416121
D-Sub9 Female
DESCRIPTION
UPSI-1208DP2 or UPSI-1208DP3 - DC UPS
V
/ V
connector counterpart
IN
OUT
Relay connector counterpart
COUNTERPART NO.
Würth Elektronik 691364300004
Würth Elektronik 691304130002
USB type B connector
D-Sub 9 Male
25